PVI Industries 399 SS A-PN Leaflet

Page of 1
Dimensions are in inches unless otherwise noted. 
For standard and optional equipment, see form # PV 6811. 
* When connected with field provided 3” x 4” adapter of the same material as required for venting (see I&M). 
PVI RESERVES THE RIGHT TO CHANGE THE DESIGN 
 AND SPECIFICATION WITHOUT NOTICE.
 
STANDARD GAS PRESSURE REQUIREMENTS
 
  
VENTING REQUIREMENTS
 
MINIMUM FLOW GAS PRESSURE: 4.5" W.C.
 
MAXIMUM STATIC GAS PRESSURE:  10.5" W.C.
 
FOR GAS PRESSURES OUTSIDE OF THIS RANGE,
 
CONTACT YOUR PVI REPRESENTATIVE.
 
  
CATEGORY IV - POSITIVE PRESSURE, CONDENSING.
 
UL CLASSIFIED FOR SCHEDULE 40, SOLID-WALL PVC OR CPVC PIPE. 
“SANI” TEMPERATURE HEATER REQUIRES CPVC VENT PIPE 
 
 
 
 
SEE INSTALLATION MANUAL FOR VENTING 
AND DIRECT COMBUSTION AIR GUIDELINES.  
 
 
STANDARD ELECTRICAL REQUIREMENTS
 
  
120V, 1Ø, 60 HZ. 
MAXIMUM AMP DRAW (TRIAL FOR IGNITION): 6 
CONTINUOUS AMP DRAW WHEN FIRING: 1.3 
CONTINUOUS AMP DRAW DURING STANDBY: 0.03
 
  
PV 6812   09/08
 
PVI INDUSTRIES, LLC 
FORT WORTH, TEXAS 76111 
(800) 784-8326   y    www.pvi.com 
This product is protected by patents in  
the U.S., Canada and Mexico. 
MODEL NUMBER   X  
199 SS A-PN  
299 SS A-PN  
399 SS A-PN  
Input Btu/h 
199,000 299,000  399,000 
GPH Recovery Rate at 40°F to 140°F 
221 
340 
444 
Approximate Shipping Weight - lbs 
1000 
1100 
1100 
Flue Connection Diameter - inches 
3 * 
Hot Outlet and Cold Inlet - NPT 
1st Hour Delivery (100°F ΔT) - gallons 
289 
397 
501 
Storage Capacity - gallons 
80 
70 
70 
PLATINUM
 ® 
• CONDENSING GAS WATER HEATER
 
STAINLESS STEEL TANK 
 
TANK SERIES 70 GALLONS