PVI Industries 500 N 225A-TPO Leaflet

Page of 1
  Recoveries based on 83% thermal efficiency.  ASHRAE 90.1 compliant for efficiency and standby loss. 
   "J" dimension is for the burner housing only.  
 
Dimensions are in inches unless otherwise specified. 
 
For standard and optional equipment, see form PV 6004.  
 
Model 
Number 
Recovery gph   
Input 
Btu/h 
Gph 
#2 Oil 
Dimensions 
(inches) 
Blower  
Motor 
Shipping 
Weight 
lbs  
40°- 120°F  40°- 140°F 
J   
HP 
Volt/Ph/Amps 
250 N 225A-TPO 
250 
200 
199,000 
1.4 
28 
17 
1/3 
115/1
∅/8 
1380 
500 N 225A-TPO 
500 
400 
399,000 
2.8 
28 
17 
1/2 
115/1
∅/10 
1400 
750 N 225A-TPO 
750 
600 
600,000 
4.3 
42 
17 
1/2 
115/1
∅/10 
1480 
1000 N 225A-TPO 
1000 
800 
800,000 
5.7 
42 
17 
1/2 
115/1
∅/10 
1520 
TURBOPOWER
®
  OIL 
 
PACKAGED WATER HEATER 
NICKELSHIELD
® 
NICKEL-PLATED STORAGE TANK 
TANK SERIES 225 GALLONS  
PV 5359  04/05 
PVI INDUSTRIES, LLC 
FORT WORTH, TEXAS 76111 
(800) 784-8326 
 
(817) 335-9531 
 
www.pvi.com 
Product is patented in the U.S., Canada, and Mexico. 
VENTING REQUIREMENTS 
-.02" TO -.06" W.C. (NEGATIVE PRESSURE) 
 
ENTIRE VENT SYSTEM SHOULD NEVER BE SIZED BASED 
UPON THE VENT CONNECTION DIAMETER EXCLUSIVELY.  
FOR PROPER SIZING, CONSULT VENTING SUPPLIER. 
STANDARD ELECTRICAL REQUIREMENTS 
CONTROL VOLTAGE: 120V, 1Ø, 60 HZ., 2 AMPS. 
  MOTOR VOLTAGE:  
  208V, 230V, AND 460V MOTORS ARE AVAILABLE BUT WILL 
  REQUIRE A SEPARATE 120V/2 amps CONTROL CIRCUIT OR 
  AN OPTIONAL CONTROL CIRCUIT TRANSFORMER. 
PVI RESERVES THE RIGHT TO CHANGE THE DESIGN 
AND SPECIFICATION WITHOUT NOTICE.