PVI Industries 1500 P 250A-TPL Leaflet

Page of 1
Product is patented in the U.S., Canada, and Mexico. 
 
PVI INDUSTRIES, LLC 
FORT WORTH, TEXAS 76111 
PV 6515  02/25/04
 
(800) 784-8326  
•  www.pvi.com 
LOW NO
x
 TURBOPOWER
®
 • PACKAGED WATER HEATER 
POLYSHIELD
®
 POLYMER-LINED STORAGE TANK 
TANK SERIES 250 GALLONS VERTICAL 
 
 
Recovery gph
   
Dimensions 
(inches) 
Blower  
Motor 
MODEL 
NUMBER 
40° - 120°F  40° - 140°F 
INPUT 
Btu/h 
Min. Inlet 
Flow Gas 
Pressure 
" W.C.   
SCAQMD Energy 
Model No. 
A B  C  HP Amps 
Shipping
Weight
#  
1000 P 250A-TPL 
1000 
800 
800,000
4.5 
8TPL 
800 MBtu/h 
33 
1/2 
1590 
1500 P 250A-TPL 
1500 
1200 
1,200,000
4.5 
12TPL 
1200 MBtu/h  50 
1-1/4 
14 
1960 
 Recoveries based on 83% thermal efficiency. ASHRAE 90.1 compliant for efficiency and standby loss. 
 With standard gas train 
 
4" x 42" Channel skids for inputs ≤ 1000 MBtu/h. 
 
4" x 53" Channel skids for inputs > 1000 MBtu/h. 
*  The information presented is for natural gas 0.6 S.G. 
  Dimensions are in inches unless otherwise specified. 
  For standard and optional equipment, see form #PV 6453. 
 
 
 
 
 
 
 
 
 
 
 
STANDARD GAS PRESSURE REQUIREMENTS: 
SEE TABLE FOR MINIMUM PRESSURE BY MODEL. 
MAXIMUM STATIC INLET GAS PRESSURE IS 10.5" W.C.  
FOR GAS PRESSURES OUTSIDE OF THIS RANGE,  
CONTACT YOUR PVI REPRESENTATIVE. 
 
VENTING REQUIREMENTS: 
-.02" TO -.06" W.C. (NEGATIVE PRESSURE). 
TYPE B VENTING. 
ENTIRE VENT SYSTEM SHOULD NEVER BE SIZED BASED UPON 
THE VENT CONNECTION DIAMETER EXCLUSIVELY. CHECK 
NATIONAL FUEL GAS CODE UNDER "FAN ASSISTED." 
 
STANDARD ELECTRICAL REQUIREMENTS: 
VOLTAGE:
 120V, 1Ø, 60 HZ., 20 AMPS. 
OTHER VOLTAGES REQUIRE AN EXTERNAL 
STEPDOWN TRANSFORMER. 
 
PVI RESERVES THE RIGHT TO CHANGE THE DESIGN AND 
SPECIFICATION WITHOUT NOTICE.