Chapter 6—Alarms
63230-300-212
Alarm Conditions and Alarm Numbers
April 2001
© 2001 Schneider Electric All Rights Reserved
94
Table 6–3: List of Default Alarms by Alarm Number
Alarm
Number
Alarm Description
Abbreviated
Display Name
Test
Register
Units
Scale
Group
Alarm
Type
Standard Speed Alarms (1 Second)
01
Over Current Phase A
Over Ia
1100
Amperes
A
010
02
Over Current Phase B
Over Ib
1101
Amperes
A
010
03
Over Current Phase C
Over Ic
1102
Amperes
A
010
04
Over Current Neutral
Over In
1103
Amperes
B
010
05
Over Current Ground
Over Ig
1104
Amperes
C
010
06
Under Current Phase A
Under Ia
1100
Amperes
A
020
07
Under Current Phase B
Under Ib
1101
Amperes
A
020
08
Under Current Phase C
Under Ic
1102
Amperes
A
020
09
Current Unbalance, Max
I Unbal Max
1110
Tenths %
010
10
Current Loss
Current Loss
3262
Amperes
A
053
11
Over Voltage Phase A–N
Over Van
1124
Volts
D
010
12
Over Voltage Phase B–N
Over Vbn
1125
Volts
D
010
13
Over Voltage Phase C–N
Over Vcn
1126
Volts
D
010
14
Over Voltage Phase A–B
Over Vab
1120
Volts
D
010
15
Over Voltage Phase B–C
Over Vbc
1121
Volts
D
010
16
Over Voltage Phase C–A
Over Vca
1122
Volts
D
010
17
Under Voltage Phase A
Under Van
1124
Volts
D
020
18
Under Voltage Phase B
Under Vbn
1125
Volts
D
020
19
Under Voltage Phase C
Under Vcn
1126
Volts
D
020
20
Under Voltage Phase A–B
Under Vab
1120
Volts
D
020
21
Under Voltage Phase B–C
Under Vbc
1121
Volts
D
020
22
Under Voltage Phase C–A
Under Vca
1122
Volts
D
020
23
Voltage Unbalance L–N, Max
V Unbal L-N Max
1136
Tenths %
010
24
Voltage Unbalance L–L, Max
V Unbal L-L Max
1132
Tenths %
010
25
Voltage Loss (loss of A,B,C, but not all)
Voltage Loss
3262
Volts
D
052
26
Phase Reversal
Phase Rev
3228
051
27
Over kVA Demand
Over kVA Dmd
2181
kVA
F
011
28
Over kW Demand
Over kW Dmd
2151
kW
F
011
29
Over kVAR Demand
Over kVAR Dmd
2166
kVAR
F
011
30
Over Frequency
Over Freq.
1180
Hundredths of Hertz
010
31
Under Frequency
Under Freq.
1180
Hundredths of Hertz
020
32
Lagging true power factor
Lag True PF
1163
Thousandths
055
33
Leading true power factor
Lead True PF
1163
Thousandths
054
34
Lagging displacement power factor
Lag Disp PF
1171
Thousandths
055
35
Leading displacement power factor
Lead Disp PF
1171
Thousandths
054
36
Over Current Demand Phase A
Over Ia Dmd
1961
Amperes
A
010
37
Over Current Demand Phase B
Over Ib Dmd
1971
Amperes
A
010
38
Over Current Demand Phase C
Over Ic Dmd
1981
Amperes
A
010
39
Over THD Voltage A–N
Over THD Van
1207
Tenths %
010
40
Over THD Voltage B–N
Over THD Vbn
1208
Tenths %
010
41
Over THD Voltage C–N
Over THD Vcn
1209
Tenths %
010
42
Over THD Voltage A–B
Over THD Vab
1211
Tenths %
010
Alarm Types are described in Table 6–4 on page 96.