Schneider Electric 4000 User Manual

Page of 216
63230-300-212
Chapter 3—Operation
April 2001
Configuring the Circuit Monitor Using The Setup Menu
23
© 2001 Schneider Electric All Rights Reserved
To set up an I/O, you must do the following:
1. Install the I/O option module following the instructions provided with the
product.
2. Use the display to select which
IOX
option is installed.
3. Use the display to configure each individual input and output. You can
also use
SMS
to configure inputs and outputs.
NOTE: After selecting which IOX option is installed, you can’t configure the
module until you have saved the changes. After saving the changes, you then
can configure the inputs and outputs.
For a description of I/O options, see
on page 69. To view the status of an I/O, see “Viewing I/O Status” on page
43. You need to know the position number of the I/O to set it up. See “I/O Point
Numbers” on page 186 
to determine this number. To set up an I/O, follow
these steps:
1. From the Main Menu, select Setup.
The password prompt displays.
2. Select your password. The default password is 0.
The Setup menu displays.
3. Select I/O.
The I/O Setup menu displays.
NOTE: Other option modules will be displayed in the I/O menu if they
are installed
4. Select the I/O option that you have installed. In this example, we selected
the I/O Extender.
Setting Up I/Os
Selecting I/O Modules
SETUP
Date & Time
Display
Communications
Meter
Alarm
I/O
Passwords
I/O
KYZ
I/O Extender