At outside temperatures below the frost-protection limit (see 
4.2.3 "System Parameters" menu, pg. 51) the
 
heating circuits are 
controlled as follows: 
•  Without wall devices: Based on a lowered room temperature 
specification of 3 °C. 
•  With wall devices: Based on the room frost-protection limit of 
the respective heating circuit of 10 °C (see "Direct Heating 
Circuit" or "Mixed Heating Circuit 1", "Mixed heating circuit 2" 
menu, parameter 08 = room frost-protection limit). 
 
An active holiday program can be cancelled in case of early 
return.  
► Press 
 button. 
► Turn input button 
î
 and switch to automatic mode. 
The active holiday program has been cancelled. 
 
Current date 
 
Current date... (current date + 250 days) 
 
An active holiday program appears in the basic display with 
information on the return date. 
 
Pos: 21 /156-Honeywell/Bedienung/Taste_Anlageninformation @ 1\mod_1207644494728_6.doc @ 9450 
 
Control during 
holidays
Cancellation
Factory setting
Setting range
Display