Honeywell T7984 B User Manual

Page of 8
T7984 A,B,C ELECTRONIC MODULATING CONTROL THERMOSTATS 
T7984A 
Output 1 analog
2œ10V 
Output 2
on/off 
Mode input
jumper 
Changeover input 
for Out 1 
Day/Night 
mode (NSB) 
Remote sensor 
option 
75°F setpoint 
limit 
Cooling and/or 
heating 
WIRING 
To install a remote duct or room temperature sensor, adust DIP 
the screw terminals and wire as shown. 
switch S6 to 0 = off and wire as shown. 
(If sensor is used, wire 1changeover sensor per 
To reverse operation of output 1 to heating, install the 
thermostat.) 
changeover contact or the changeover sensor across 
Fig. 2. T7984A Wiring 
Input (2-10 Vdc) 
24 Vac 
Common 
2-10 Vdc valve or VAV 
analog actuator 
Duct 
or 
Room 
Not used 
Remote 
sensor input 
(0 Vac) 
Output 1 
2-10 Vdc 
Changeover 
input for Out 1 
Changeover 
contact 
OR  Changeover 
sensor 
24 Vac 
Power supply 
(0 Vac) 
24 Vac Transformer 
SEQUENCE  
SETPOINT DIAL CENTERED 
End
Heating mode 
End
Opened 
Cooling mode
Device 
Device
changeover
100% 
opened 
opened
input active 
10 Vdc 
10 Vdc 
50% 
End  
0%  
Closed 
End 
Device 
closed 
closed 
Device 
Temperature increase 
OUTPUT 1 ANALOG 
Fig. 3. T7984A Sequence 
DIP SWITCH SETTINGS 
REMOTE SENSOR 
MAIN SENSOR 
S6 
LOCAL INTERNAL 
REMOTE SENSOR  0 
<< Not used 
ON = 1 
OFF = 0  6 7 8 
Fig. 4. T7984A Dip Switch Settings 
95C-10815–2