T6570, T8570 SERIES DIGITAL FAN-COIL THERMOSTATS 
Table 5. Thermostat Parameter Options 
Parameter 
ID 
Description 
°C Scale 
°F Scale 
Default 
Values 
Default 
Values 
Temperature Scale  tS 
Allows selection of either °C or °F scale  Yes 
– 
No 
– 
Dead Band 
db 
Setting deadband (Zero Energy Band)  2 
2, 3, 4 
3, 4, 5 
Heat or Cool 
Operating Mode 
OP 
Setting operating mode on single relay, 
non-changeover models, to either Heat 
or Cool 
0: cool 
1: heat 
0: cool 
1: heat 
Unoccupied Cooling 
Setpoint 
uC 
Program unoccupied cooling setpoint 
for energy savings. 
25 
25 to 30 
77 
77 to 90 
Unoccupied Heating 
Setpoint 
uH 
Program unoccupied heating setpoint 
for energy savings 
18 
10 to 18 
65 
50 to 65 
Minimum Cooling 
Off Time 
CO  Setting cooling off-time for short cycle 
prevention. 
0, 3, 4, 5 
0, 3, 4, 5 
Minimum Heating 
Off Time 
HO  Setting heating off-time for short cycle 
prevention. 
0, 3, 4, 5 
0, 3, 4, 5 
Minimum Cooling 
Setpoint (Low Limit) 
CL 
Sets the minimum allowable cooling 
setpoint. 
10 
10 to 30 
50 
50 to 90 
Maximum Heating 
Setpoint (High Limit) 
HL 
Sets the maximum allowable heating 
setpoint. 
30 
10 to 30 
90 
50 to 90 
Energy Savings 
Configuration 
ES 
Activate energy savings mode by a 
choice of either contact closure or 
contact opening. 
1: normally open 
0: normally closed 
1: normally open 
0: normally closed 
Display of Room 
Temperature 
rt 
Allows installer to restrict temperature 
display to set point only.  With this 
parameter, the unit will only display the 
set point temperature.  Useful where 
setpoint limits (HL and CL) will affect 
control performance and Room 
Temperature display will disagree with 
user setpoint. 
1: room temp. 
0: setpoint only 
1: room temp. 
0: setpoint only 
WIRING  
Table 6. Leadwire Color Code (if fitted) 
Terminal 
Color 
Use 
Black (BK) 
L1 (Hot) 
White (WH) 
L2 (N) 
Orange (OR) 
Heat 
Yellow (YL) 
Cool 
Gray (GY) 
Damper 
Violet (VI) 
Fan Common 
Red (RD) 
Fan Low 
Blue (BU) 
Fan Medium 
Brown (BN) 
Fan High 
10 
– 
Energy Mgt. 
System
11 
– 
Fig. 6. Wiring 2-pipe cool-only thermostat with fan On/Auto
switch. 
95C-10897–6