T7351 COMMERCIAL PROGRAMMABLE THERMOSTAT
63-2666—03
4
CAUTION
Equipment Damage Hazard.
Can damage the TIM connection beyond repair.
Disconnect the TIM cable prior to opening or closing 
the thermostat cover.
NOTE: Allow sufficient clearance below the thermostat to 
plug in the TIM cable.
Install the remote-mounted sensor(s) about 5 ft. (1.5 m) above 
the floor in an area with good air circulation at average 
temperature. (See Fig. 2.)
NOTE: Only TR21 models with neither setpoint adjust-
ment nor bypass can be used for temperature 
averaging.
Fig. 2. Typical Location of Thermostat or Remote-Mounted 
Sensor.
IMPORTANT
To avoid electrical interference, which can cause 
erratic performances, keep wiring runs as short as 
possible and do not run thermostat wires adjacent to 
the line voltage electrical distribution systems. Use 
shielded cable (Belden type 8762 or equivalent for 
2-wire). The cable shield must be grounded only at 
the controlled equipment case.
Mounting Subbase
The subbase mounts horizontally or vertically.
IMPORTANT
• When using the internal temperature sensor, the 
device must be mounted horizontally (with the LCD 
facing upwards). Precise leveling is not needed.
• When using remote sensors, thermostat mounting 
orientation does not matter.
Wall mounting (using standard drywall screws) is standard. 
Mounting to a 2 in.(50.8 mm) by 4 in. (101.6 mm) wiring box 
can be accomplished:
— for a horizontal box, no extra hardware is required.
— for a vertical box, part 209651A is required.
— Mount to European standard wall box 2.4 in. (having 61 mm 
between mounting screws in a horizontal line) with or 
without adaptive hardware.
1. Position and level the subbase.
NOTE: A level wallplate is only for appearance. The 
thermostat functions properly when not level.
2. Use a pencil to mark the mounting holes. 
(Refer to Fig. 6.)
3. Remove the subbase from the wall and drill two 3/16 in. 
(4.76 mm) holes in the wall (if drywall) as marked. For 
firmer material such as plaster or wood, drill two 7/32 in. 
(5.56 mm) holes.
4. Gently tap anchors (provided) into the drilled holes until 
flush with the wall.
5. Position the subbase over the holes, pulling wires 
through the wiring opening.
6. Loosely insert the mounting screws into the holes.
7. Tighten mounting screws.
Fig. 3. Four TR21 Sensors providing a Temperature 
Averaging Network for T7351 Thermostat.
5 FEET
(1.5 METERS)
YES
NO
NO
NO
M4823A
M29184
T4
T3
T
T
SUBBASE
TR21
T
T
TR21
T
T
TR21
T
T
TR21
T4 T3 
T7350 SUBBASE 
TR21-A
T4 T3 
TR21-A
T4 T3