PRODUCT DESCRIPTION
WebVision™ is a web-based building manager that allows 
contractors and facility managers to view and command 
HVAC controllers installed at their sites. It communicates over 
the LonWorks
®
 network to perform building management 
control of various devices and controllers through a web 
browser. The WebVision Bundle (WWS-VL1A1000) includes 
the WebVision controller pre-installed with a LON 
communications card, and power supply.
WebVision is capable of:
• Discovering unitary controllers connected to WebVision
• Configuring controllers using configuration wizards
• Monitoring, raising, and e-mailing alarms on controller 
points and system events
• Configuring and collecting trends on points
• Driving scheduled occupancy states
• Managing energy through Demand Limit Control (DLC)
• Providing single point of entry into the system to perform all 
the above mentioned tasks.
• Managing access to information through user privileges
• Providing IT-friendly network interface for easy access and 
management
WebVision acts as an offline configuration tool that helps the 
contractor to configure site project that consists of multiple 
unitary controllers. The contractor can commission all the 
controllers by connecting through a LAN, WAN, or Dial-up.
WebVision also acts like a network time master to synchronize 
time and date in devices connected to it with its own time and 
date or with the Internet time servers. Its Device Discovery 
feature enables you to discover online devices. You can 
manage users and control their access to different resources 
in the system. The System Administrator can configure 
network settings, site information settings, system and control, 
network data and time settings, and new module installation.
Approvals
UL 916, C-UL listed to Canadian Standards Association (CSA) 
C22.2 No. 205-M1983 “Signal Equipment”, CE, FCC part 15 
Class A, C-tick (Australia)
CAUTION
Make sure that there is not more than one 
WebVision accessing the same Lon
®
 network 
simultaneously. If more than one WebVision 
accesses the same Lon network simultaneously, 
there may be problems in downloading and 
uploading parameters. 
NOTE: WebVision is compatible with Microsoft
®
 Internet 
Explorer
®
 (IE) 6.0 SP2 or higher. Suggested screen 
resolution is 1280x1024 pixels.
IMPORTANT
Make sure that there is only one WebVision 
accessing the L
ON
W
ORKS
 network at a given point in 
time. If more than one WebVision accesses the 
same L
ON
W
ORKS
 network simultaneously, ensure 
that its logical address is unique in the network to 
avoid address conflicts. For a L
ON
W
ORKS
 network, 
logical address refers to Subnet/NodeID.