Emerson EC2-391 User Manual

Page of 4
EC2-391_65136_EN_R01.doc 
Replacement for 00 
4 / 4  
PCN: 865 022       21.09.2007 
 
 
EC2-391 Display Case and Coldroom Controller 
Operating Instructions 
GB 
Formula for Mean Factors A0, r8, r9 
Temperature calculation by the following formula: 
     Temperature = Air
in
 * (1 - Mean Factor / 100) + Air
out
 * Mean Factor / 100 
Examples: 
Mean factor = 0    ,   Temperature = Air in 
Mean factor = 100,   Temperature = Air out 
Mean factor = 50   ,   Temperature = Average between Air-in and Air-out 
Alarm Codes 
E0   Coil in sensor alarm 
E1   
Coil out sensor alarm 
E2   
Air-in sensor alarm This Alarm Code is inhibited if no air-in sensor used 
(A0, r8 and r9 = 100) 
E3   Air-out sensor alarm This Alarm Code is inhibited if no air-out sensor used 
(A0, r8 and r9 = 0) and fin sensor installed (d2 = 1) 
E4   Fin sensor alarm This Alarm Code is inhibited if no fin sensor used (d2 = 0) 
Explanations for E0 … E4 Alarms: No sensor connected, or the sensor and/or the 
sensor cable is broken or short-circuited. 
Er 
Data error display - out of range 
 
Data send to the display is out of range. 
AH  High temperature alarm 
AL 
Low temperature alarm 
AE  Thermostat emergency operation 
 
Air sensor failure, system is in continuous cooling mode 
AF  Valve Status 
 
Valve closed due to compressor safety loop active 
Ao 
Superheat, emergency operation 
 Sensor(s) 
failure 
Ar 
No refrigerant flow detected 
 
No refrigerant flow was detected 
Au 
Valve open 100% for more than 10 minutes 
dt 
Forced defrost termination (time or temperature) 
Ft 
Forced fan startup (time or temperature) 
 
Messages 
---  
No data to display 
 
The display will show an “---” at node start up and  when no data is send to 
the display. 
In  
Reset to default values activated 
 
The display will show an “In” when the factory default configuration data set 
is initialized. 
Id  
Wink request received 
 
The display will show a flashing “Id” when the wink request was received. 
The flashing “Id” will be shown on the display until the service button will 
be pressed, or a 30 min delay timer will expire or a second wink request is 
received.  
OF   Node is offline 
 
The node is offline and no application is running. This is the result of a 
network management command and will happen for example during node 
installation. 
dS Defrost 
standby 
dP Pump 
down 
dF Defrost 
cycle 
dd 
Defrost drain delay 
dI Defrost 
injection 
delay 
du 
Defrost start-up delay 
Cn Cleaning 
CL
 
Alarms are cleared 
Visualising Data: LON Monitoring Server 
The  EC2-391  has a LON communication interface enabling the controller to be 
directly connected to a Monitoring Server. It can be connected by using the optional 
cable assembly to a LON network (ECC-014, Order No. 804 381, with RJ45 to 
open, cable length 3m). 
Neuron ID / Service PIN: 
The service pin is available on the display. It is used to identify the controller in a 
LON network. Press the    button for app. 1 second to send the Neuron ID. The 
LED in the left upper corner will indicate the transmission of the Neuron ID.  
The default settings may be modified remotely from the Monitoring Server via the 
LON network. Consult the Monitoring Server user manual for more information. 
It is also possible to display live graphical data on the server or to log data 
containing the control temperature at defined intervals. 
 
 
 
 
 
 
 
 
 
 
 
 
Emerson Electric GmbH & Co OHG is not to be held responsible for erroneous 
literature regarding capacities, dimensions, applications, etc. stated herein. 
Products, specifications and data in this literature are subject to change without 
notice. The information given herein is based on technical data and tests which 
EMERSON believes to be reliable and which are in compliance with technical 
knowledge of today. It is intended only for use by persons having the appropriate 
technical knowledge and skills, at their own discretion and risk. Since conditions of 
use are outside of EMERSON’s control we cannot assume any liability for results 
obtained or damages occurred due to improper application. 
This document replaces all former versions 
 
Emerson Electric GmbH & Co OHG - Postfach 1251 - Heerstraße 111  -  D-71332 Waiblingen  -  Germany  -  Phone .49-(0)7151-509-0  -  Fax .49-(0)7151-509-200 
 
www.emersonclimate.eu