Emerson Process Management Series 9110 User Manual

Page of 74
Field Wiring 
4-2 
CI-9110 
Table 4-1 - Terminal Identification For Analog Input Models 
 
 
TERMINAL 
LEGEND 
 
FUNCTION 
 
TB1-1 
TB1-2 
TB1-3 
TB1-4 
TB1-5 
TB1-6 
 
TB2-1 
TB2-2 
TB2-3 
TB2-4 
TB2-5 
TB2-6
 
 
Green Screw
 
 
Unused 
Unused 
Analog In+ (Command Input) 
Analog In-  (Command Input) 
Guard 
Guard Com 
 
Unused 
Current Out + 
Current Out - 
Supply + 
Supply - 
Unused 
 
Chassis
 
 
Table 4-2 - Terminal Identification For Raise/Lower Models 
 
 
TERMINAL 
LEGEND 
 
FUNCTION 
 
TB1-1 
TB1-2 
TB1-3 
TB1-4 
TB1-5 
TB1-6 
 
TB2-1 
TB2-2 
TB2-3 
TB2-4 
TB2-5 
TB2-6
 
 
Green Screw
 
 
Raise           (Command) Input) 
Raise Com   (Command) Input) 
Lower          (Command) Input) 
Lower Com  (Command) Input) 
Guard +  
Guard Com 
 
Remote/Local Status 
Current Out + 
Current Out - 
Supply + 
Supply - 
Unused 
 
Chassis
 
 
Note:  Raise, Lower & Guard Terminals are 
non-polarized and opto-isolated. 
 
4.3  ANALOG VOLTAGE INPUT (1-5 V) WITH GUARD
 
 
A voltage signal can be used as the Command Input as shown in Figure 4-2. In this 
example, a Bristol Babcock, METATONE B, Analog FSK Tone Receiver (Model 8772-31B) 
provides the input to the Remote Set Regulator. Switch SW2-8 must be set to the OPEN 
position to accommodate a 1-5 V input.