Lucent Technologies Release 7 User Manual

Page of 2657
DEFINITY Enterprise Communications Server Release 7 
Maintenance for R7r  
555-230-126  
Issue 4
June 1999
Maintenance Object Repair Procedures 
9-681
DS1 CONV-BD 
9
u. This error indicates that excessive slips have occurred on the fiber link 
between the DS1 CONV board and the Fiber Endpoint. See MO SYNC for 
diagnosing slip problems.
System Technician-Demanded Tests: Descriptions 
And Error Codes
Always investigate tests in the order presented in the table below. By clearing 
error codes associated with the 
Failure Audit for example, you may also clear 
errors generated from other tests in the testing sequence. Tests 788 and 789 are 
executed by the TN574 DS1 Converter circuit pack only.
NOTE:
Test #984 is not an actual demand maintenance test. This test number is 
used to report results of the clear firmware-counters command. Refer to 
the table for Test #949 to interpret ABORT codes for Test #984.
Reset Test (#787)
This test is destructive.
DS1 CONV circuit pack is reset via the reset board command. When the circuit 
pack is reset, firmware executes a series of diagnostic tests on the circuit pack. 
The results of these tests are queried from the board when the board is inserted 
after completion of the reset sequence. If any one of the diagnostic test fails, the 
error log will have an entry of error type 1 for this circuit pack location, and the 
alarm log will have an entry of ON-BOARD MAJOR alarm.
The reset sequence will take about one minute to complete.
Order of Investigation
Short Test 
Sequence
Long Test 
Sequence
Reset Board 
Sequence
D/ND
1
1.
 D = Destructive; ND = Nondestructive
Failure Audit (#949)
X
X
ND
DS1 Facilities Connectivity Test (#790)
X
D
Far-end DS1 CONV Circuit Pack Loopback 
Test (#788) (Executed by TN574 only)
X
D
Far-end Lightwave Transceiver Loopback 
Test (#789) (Executed by TN574 only)
X
D
Board Options Audit (#795)
X
X
ND
Reset Test (#787)
X
D