Lucent Technologies Release 7 User Manual

Page of 2657
DEFINITY Enterprise Communications Server Release 7 
Maintenance for R7r  
555-230-126  
Issue 4
June 1999
Maintenance Object Repair Procedures 
9-846
EXT-DEV ADMIN? Y (External Device Alarm) 
9
Error Log Entries and Test to Clear Values
NOTE:
The loss of -48 volt power prevents detection of an external device alarm. 
AC-POWER, CARR-POW, and DC-POWER alarms could indicate the loss 
of the external device alarm -48 volt power source. ALARM-PT alarms may 
also indicate a loss of power. When analog line ports are administered as 
analog line external device alarms loss of -48 volts prevents detection of an 
external device alarm.
System Technician-Demanded Tests: Descriptions 
and Error Codes
Always investigate tests in the order presented in the table below when 
inspecting errors in the system. By clearing error codes associated with the 
Battery & Battery Charger Query Test, you may also clear errors generated from 
other tests in the testing sequence.
External Device Alarm Test (#120)
The External Device Alarm Test requests the state of the External Device Alarm 
from a Maintenance circuit pack and reports the results. The test has no effect on 
the external device itself
Error 
Type
Aux 
Data
Associated Test
Alarm 
Level
On/Off 
Board
Test to Clear Value
0
0
Any
Any
Any
test eda-external-device-alrm 
physical location r 2 or 6
1 or 5
Any
External Device 
Alarm Test (#120)
Any
OFF
test eda-external-device-alrm 
physical location r 2 or 6
Order of Investigation
Short Test 
Sequence
Long Test 
Sequence
D/ND
1
1.
D = Destructive; ND = Nondestructive
External Device Alarm Test (MAJOR port) (#120)
X
X
ND
External Device Alarm Test (MINOR port) (#120)
X
X
ND
External Device Alarm Test (WARNING port) (#120)
X
X
ND