Maintenance Object Repair Procedures 
9-1026
MEM-BD (32MB Memory Circuit Pack) 
9
MEM-BD (32MB Memory Circuit 
Pack)
The memory circuit packs contain the system software which is executed after it 
is loaded from tape or disk. The processor and the memory circuit packs form 
the most critical component for all system operation.
The processor must be able to access the memory for all system activity or the 
system will go into SPE-down mode. In SPE-down mode, fatal memory errors 
may show up as processor circuit pack errors.
Each memory circuit pack has 32 Mbytes of capacity. The SPE carrier(s) contain 
four dedicated slots for Memory circuit packs. Depending on its size, the system 
uses from two to four of these slots. Memory circuit packs must reside in 
contiguous slots, starting Memory slot one.
Each Memory circuit pack contains its own error detection and correction (EDC) 
circuit, parity checker and burst read function.
The EDC circuit operates by checking the contents of memory both as memory 
locations are accessed by the Processor and periodically by a built-in 
"scrubbing" function. The scrubbing function checks for errors through the entire 
Memory circuit pack every 111 seconds. It flags and corrects single-bit errors 
automatically and flags (but does not correct) multiple bit errors. If the EDC 
circuit fails, the Memory circuit pack will not be able to detect and correct single 
bit errors or detect and flag multiple bit errors. If a single or multiple bit error 
occurs, the system may not continue to operate correctly.
The Memory parity checker detects bad parity over the Processor Bus when any 
Bus Master writes memory. It also generates parity (for checking by the 
MO Name (in 
Alarm Log)
Alarm 
Level
Initial Command to Run
1
1.
UU is the cabinet number (always 1, not required). With simplex SPE, carrier designation is not 
required. With duplicated SPEs, carrier a or b must be specified. 
S is the number of the circuit 
pack slot (1 to 4 for Memory slots). If the slot number is 
not specified, all Memory circuit packs 
in the specified carrier will be tested.
Full Name of MO
MEM-BD
MAJOR
2
2.
After a spontaneous SPE interchange has occurred, the Alarm Log retains for three hours a 
record of any MAJOR ON-BOARD alarm against an SPE component that took place before the 
interchange. If a spontaneous interchange has occurred (as indicated by STBY-SPE error type 
103 or the display initcauses screen), and handshake is down, (check with status spe), 
replace the alarmed circuit pack on the standby SPE. If handshake is up, execute a test long 
clear
 of the alarmed circuit pack and follow recommended procedures.
test memory UUCS l
32M Memory Circuit Pack
MEM-BD
MINOR
test memory UUCS s
32M Memory Circuit Pack
MEM-BD
WARNING
32M Memory Circuit Pack