Lucent Technologies Release 7 User Manual

Page of 2657
DEFINITY Enterprise Communications Server Release 7 
Maintenance for R7r  
555-230-126  
Issue 4
June 1999
Maintenance Object Repair Procedures 
9-1321
POWER 
9
Battery and Charger for DC-Powered Systems
NOTE:
This MO applies to the J58890CE and the J58890CH-1 with large battery 
holdover.
This MO represents the battery backup unit found in AC-powered multi-carrier 
cabinets. Because the system does not recognize the type of external power, this 
MO exists in DC-Powered multi-carrier cabinets but serves no functional 
purpose. In such cabinets, all POWER tests should always either pass or abort, 
and no POWER alarms should be raised.
DEFINITY Systems support two different cabinet types: multi-carrier and 
single-carrier. Single-carrier cabinets are used only for EPNs. Both cabinet types 
may be powered by either AC or DC external power source. Environmental 
maintenance differs according to cabinet type and external power supply. 
MO Name (in 
Alarm Log)
Alarm 
Level
Initial Command to 
Run
1
1.
UU is the cabinet number indicated in the PORT field from the Alarm or Error Log.
Full Name of MO
POWER
MINOR
test environment 
UU 
Battery & Battery Charger