Maintenance Object Repair Procedures 
9-1381
SNC-BD (Switch Node Clock Circuit Pack) 
9
SNC-BD (Switch Node Clock Circuit 
Pack)
The Switch Node Clock (SNC) TN572 circuit pack is part of the Center Stage 
Switch (CSS) configuration. It resides in a switch node carrier that alone or with 
other switch nodes make up a CSS. In a high reliability system (duplicated SPE, 
simplex PNC), each SNC is duplicated such that there are two SNCs on each 
switch node carrier. In a critical reliability system (duplicated SPE and PNC), 
each switch node is fully duplicated, and there is one SNC on each switch node 
carrier. SNCs are placed in slots 10 and 12 of the switch node carrier.
The active SNC communicates with each circuit pack in the switch node carrier 
over the serial channel bus on the backplane. In addition, the active SNC 
provides timing to the circuit packs in the switch node carrier via the clock 
busses. The active SNC uses Timing Priority Number (TPN) links with each 
Switch Node Interface (SNI) and the other SNC to receive and distribute TPNs. 
TPNs are used for setting up the correct timing distribution for the switch node 
carrier. The active SNC receives timing for the switch node carrier from each SNI 
circuit pack in the carrier and chooses the SNI with the best timing reference for 
the switch node carrier timing signal the SNC puts out on the clock busses. The 
timing reference for each SNI is derived from the fiber signal to each SNI. The 
active SNC chooses the SNI to receive timing from by choosing the SNI with the 
lowest numbered TPN which means that the SNI is closest to the system timing 
source. The active SNC also verifies that the SNI reference signal is good before 
using that SNI as the timing reference for the switch node carrier. The active SNC 
then supplies this timing over the clock busses on the backplane to all the SNI 
and SNC circuit packs in the carrier. For more information on timing 
synchronization including how the SNC fits into the overall synchronization 
configuration, see the SYNC section.
MO Name (in 
Alarm Log)
Alarm 
Level
Initial Command to Run
1
1.
UU is the universal cabinet number (1 for PPN, 2 - 44 for EPNs). C is the carrier designation
(A, B, C, D, or E). SS is the number of the slot in which the circuit pack resides (10 or 12).
Full Name of MO
SNC-BD
MAJOR
test board UUCSS s
SNC Circuit Pack
SNC-BD
MINOR
test board UUCSS s
SNC Circuit Pack