DEFINITY Enterprise Communications Server Release 7 
Maintenance for R7r  
555-230-126  
Issue 4
June 1999
Maintenance Object Repair Procedures 
9-1543
STRAT-3 (Stratum 3 Clock) 
9
This error indicates that the Tone-Clock circuit pack in the master port 
network is not a TN780. If duplicate Tone-Clock circuit packs exist in the 
master port network, this error may mean that one or both Tone-Clock 
circuit packs are not TN780s. Verify that the Tone-Clock(s) in the master 
port network are TN780s.
System Technician-Demanded Tests: Descriptions 
and Error Codes
Always investigate tests in the order presented in the following table when 
inspecting errors in the system. By clearing error codes associated with the 
Stratum 3 Clock Alarm Query Test, for example, you may also clear errors 
generated from other tests in the testing sequence.
The test synchronization commands also runs the Test Synchronization test 
(test #417). Test 417 is described in the SYNC section.
Stratum 3 Clock Alarm Query (#649)
This test queries the Stratum 3 clock for its alarm status and reports the results of 
the query. The Stratum 3 clock provides the system with the following six alarm 
indications via the TN780 Tone-Clock circuit pack:
Reference A failed or CI card A failed.
Reference B failed or CI card B failed.
One power supply failed.
All power supplies failed.
One clock unit failed.
All clock unit(s) failed.
!
CAUTION:
The removal of a card in the Stratum 3 clock may cause alarm(s) to be 
resolved and the query test to pass. However, the removed cards should 
still be replaced to restore the Stratum 3 clock to full service.
Order of Investigation
Short Test 
Sequence
Long Test 
Sequence
D/ND
1
1.
D = Destructive, ND = Non-destructive
Stratum 3 Clock Alarm Query (#649)
X
X
ND