Maintenance Object Repair Procedures
9-1552
SW-CTL (Switch Control)
9
Error Log Entries and Test to Clear Values
Notes:
a. A 1 error indicates that there has been 8 or more Processor Port Network
circuit pack removals in less than 15 minutes. This action may be forced
manually by removing power to a port carrier or pulling out at least 8 port
circuit packs within 15 minutes. The generation of this error may indicate
that there is a problem with the Switch Control circuit on the MSSNET
circuit pack or that there is a problem with the TDM bus. Three successful
completions of the Control Channel test (#94) will resolve the MAJOR
alarm caused by this error.
manually by removing power to a port carrier or pulling out at least 8 port
circuit packs within 15 minutes. The generation of this error may indicate
that there is a problem with the Switch Control circuit on the MSSNET
circuit pack or that there is a problem with the TDM bus. Three successful
completions of the Control Channel test (#94) will resolve the MAJOR
alarm caused by this error.
b. A 2 error indicates that the Switch Control Channel Transmission test (#94)
failed. This error may not cause a Switch Control alarm if Error Type 769 is
also present since this error may actually be caused by the loss of clock
also present since this error may actually be caused by the loss of clock
Table 9-590.
Switch Control Error Log Entries
Error
Type
Aux
Data
Associated Test
Alarm
Level
On/Off
Board
Test to Clear Value
0
1
1.
Indicates that an alarm was raised but the associated error could not be entered into the hardware error
log due to a momentary overload condition. Run the short test sequence and refer to the appropriate test
description for tests that fail.
log due to a momentary overload condition. Run the short test sequence and refer to the appropriate test
description for tests that fail.
0
Any
Any
Any
test switch-control [a|b] r 3
1(a)
Control Transmission
Test (#94)Channel
Test (#94)Channel
MAJOR
2
2.
After a spontaneous SPE interchange has occurred, the Alarm Log retains for three hours a record of any
MAJOR ON-BOARD alarm against an SPE component that took place before the interchange. If a
spontaneous interchange has occurred (as indicated by STBY-SPE error type 103 or the display
initcauses screen), and such an alarm is logged against SW-CTL, then replace the standby MSSNET
circuit pack using the "lock-and-power-down" procedure described in
MAJOR ON-BOARD alarm against an SPE component that took place before the interchange. If a
spontaneous interchange has occurred (as indicated by STBY-SPE error type 103 or the display
initcauses screen), and such an alarm is logged against SW-CTL, then replace the standby MSSNET
circuit pack using the "lock-and-power-down" procedure described in
ON
test switch-control [a|b] r 3
2(b)
Control Channel
Transmission Test (#94)
Transmission Test (#94)
MAJOR
2
ON
test switch-control [a|b] r 3
150(c)
Any
None
MAJOR
2
ON
test switch-control [a|b] l c
257(d)
Any
None
769(e)
None
1025(f)
Control Channel
Interface Test (#92)
Interface Test (#92)
MAJOR
2
ON
test switch-control [a|b] r 2
1281(g)
None
1537(h)
Switch Control Reset
Test (#93)
Test (#93)
MAJOR
2
ON
test switch-control [a|b] l r 2
1793(i)
None
2561(j)
None
WARNING
OFF