Lucent Technologies Release 7 User Manual

Page of 2657
DEFINITY Enterprise Communications Server Release 7 
Maintenance for R7r  
555-230-126  
Issue 4
June 1999
Maintenance Object Repair Procedures 
9-1590
SYS-LINK (System Links) 
9
Display Errors/Alarms
The output of the display errors or display alarm commands shows the location 
of the system link for entries with a Maintenance Name of SYS-LINK. You can 
restrict the scope of the output of these commands by specifying sys-link in the 
Category
 field 
on the input form. The link type and channel number, if any, are 
listed under the 
Alt Name
 field of the report.
List sys-link
The list sys-link command lists all system links (location, link type, and channel 
number) present in the system.
NOTE:
In case of the X.25 link type, a single endpoint carries multiple links. A 
combination of the endpoint and channel number is used to uniquely 
identify the link. All other links can be uniquely identified by their endpoints.
Common Procedure for Repairing Link Problems
The state of a system link is dependent on the state of the various hardware 
components that it travels over. To resolve any problems associated with a 
system link, use the following procedure.
The switch maintains a list of hardware components over which the link travels, 
called the hardware path. There are two hardware paths: the current hardware 
path and the faulted hardware path for each of the system links. The current 
hardware path is present only for those links that are currently up. When a link is 
down, the current hardware path is empty. The faulted hardware path is always 
present once the link has gone down and is 
not cleared when the link 
subsequently recovers. The faulted path preserves the path that the link 
traversed when it last went down. The time at which the faulted path was last 
recorded is preserved and is accessible through the status sys-link 
location 
and list sys-link commands. Therefore, the focus of attention for problems which 
do not involve a link that is down is the current hardware path. If the link is down, 
faulted hardware path is the focus of attention.
The status sys-link 
location command shows the state of both the hardware 
paths (current and faulted) along with the state of each of the components in the 
hardware path. When analyzing any system link problem
1. Look for alarms on the components listed under desired hardware path. 
2. If any alarms are present, then follow the maintenance procedures for the 
alarmed components to clear those alarms first.
NOTE:
For systems using ATM EI PNC (TN2238 circuit pack) and where link 
alarms are present, refer to 
‘ATM-BCH (ATM B-Channel Trunk)’’
 and 
th
 section in 
Chapter 5
.