Lucent Technologies Release 7 User Manual

Page of 2657
DEFINITY Enterprise Communications Server Release 7 
Maintenance for R7r  
555-230-126  
Issue 4
June 1999
Maintenance Object Repair Procedures 
9-1600
SYSAM (Circuit Pack) 
9
SYSAM (Circuit Pack)
The System Access and Maintenance (SYSAM) circuit pack, TN1648:
Is a required component of the SPE Complex
Monitors the sanity of the RISC Processor circuit pack and environmental 
conditions
Provides the serial interface for the G3-MT terminal and the 
communication interface to INADS or other service locations for alarm 
reporting and remote maintenance capability
Provides the Time-Of-Day Clock for the system.
FAIL
The System Printer Link CANNOT be established. 
recommended maintenance strategy.
PASS
The System Printer Link is up.
MO Name (in 
Alarm Log)
Alarm 
Level
Initial Command to Run
1
1.
UU is the cabinet number (always 1, not required). C is the carrier designation (a or b). With
simplex SPE the carrier location is not required. With duplicated SPEs, carrier a or b must be
specified.
Full Name of MO
SYSAM
MAJOR
2
2.
After a spontaneous SPE interchange has occurred, the Alarm Log retains for three hours a
record of any MAJOR ON-BOARD alarm against an SPE component that took place before
the interchange. If a spontaneous interchange has occurred (as indicated by STBY-SPE error
type 103 or the display initcauses screen), and handshake is down, (check with status spe),
replace the alarmed circuit pack on the standby SPE. If handshake is up, execute a test long
clear
 of the alarmed circuit pack and follow recommended procedures.
test maintenance UUC l
System Access and 
Maintenance circuit pack
SYSAM
MINOR
test maintenance UUC s
System Access and 
Maintenance circuit pack
SYSAM
WARNING
test maintenance UUC s
System Access and 
Maintenance circuit pack
Table 9-603.
TEST #215 Link Retry Test  — Continued
Error 
Code
Test 
Result
Description/ Recommendation
Continued on next page