Lucent Technologies Release 7 User Manual

Page of 2657
DEFINITY Enterprise Communications Server Release 7 
Maintenance for R7r  
555-230-126  
Issue 4
June 1999
Maintenance Object Repair Procedures 
9-1704
TDM-BUS (TDM Bus) 
9
TDM Bus Fault Detection and Isolation
TDM Bus are usually caused by one of the following:
A defective circuit pack connected to the backplane
Bent pins on the backplane
Defective bus cables or terminators
It is possible that a circuit pack can cause a TDM Bus fault and still exhibit 
trouble-free operation. For example, insertions of any circuit pack into a slot with 
TDM Bus terminations may bend the backplane pins and short two leads 
together. Since the TDM Bus is a shared resource, identification of the cause of a 
TDM Bus fault can be difficult. If a TDM Bus problem is suspected, run the test 
tdm P
 command. If any of the resulting tests fail, you must perform a manual 
TDM Bus isolation procedure to identify the cause of the problem.
!
WARNING:
Since the TDM Bus fault isolation procedure involves removing circuit packs 
and possibly disconnecting entire carriers, the procedure is extremely 
destructive to the port network that contains the TDM Bus being tested. If 
possible, arrange to perform this procedure at a time when traffic is 
minimal.
As circuit packs are removed or entire carriers are disconnected, any active calls 
terminating on those circuit packs or carriers will be dropped. If you have any 
hints about a particular circuit pack that may be causing the TDM Bus problem 
investigate those before performing this procedure (for example, look at any 
circuit packs that were inserted into the PN just before the TDM bus problem 
appeared.
When straightening or replacing backplane pins in a carrier that contains a 
CFY1B Current Limiter, power to the 
cabinet must be removed. When 
straightening or replacing backplane pins in a carrier that does NOT contain a 
CFY1B Current Limiter, power to that 
carrier must be shut off. Failure to follow this 
procedure may result in damage to circuit packs and power supplies, and can 
be hazardous to the technician.
NOTE:
Maintenance software requires TN748 or TN420 Tone Detector circuit pack 
to test the TDM Bus. Before starting these procedures, make sure that one 
of these is installed in the port network being investigated.
Procedure 1
This procedure is an attempt to isolate the TDM Bus fault to circuit packs that are 
essential to the system operation. For each of the following circuit packs in the 
port network where the TDM Bus fault appears, perform Procedure 1.