Cal Flame A734L User Manual

Page of 32
LTR20091024, Rev. A
8
Electrical Requirements
Electrical Requirements – US and Canada
240 Volt Electrical Installation
All 240V spas must be permanently connected (hardwired) to the power 
supply.  These  instructions  describe  the  only  acceptable  electrical  wiring 
procedure. Spas wired in any other way will void your warranty and may 
result in serious injury.
This is the only acceptable electrical wiring procedure. Spas wired in any 
other way will void your warranty. See the wiring diagram on page 11.
When installed in the United States, the electrical wiring of this spa must 
meet the requirements of National Electric Code, ANSI/NFPA 70-2008 and 
any applicable local, state, and federal codes. The electrical circuit must 
be installed by an electrical contractor and approved by a local building / 
electrical inspector.
GFCI and Wiring Requirements
The power supplied to the spa must be on a dedicated GFCI protected 
circuit  as  required  by  ANSI/NFPA  70  with  no  other  appliances  or  lights 
sharing the power.
Use copper wire with THHN insulation. Do not use aluminum wire.
Use the table on the next page to determine your GFCI and wiring require-
ments.
When NEC requires the use of wires larger than #6 AWG, install a junction 
box near the spa and use #6 AWG wire between the junction box and the 
spa.
Wire runs over 85 feet must increase wire gauge to the next lower num-
ber.  For  example:  A  normal  50  amp 
GFCI with four #8 AWG Copper wires 
run over 85 feet would require you to 
go to four #6 AWG copper wires.
Read  and  follow  the  heater  manufac-
turer’s  safety  and  installation  instruc-
tions prior to installation and operation. 
Incorrect installation may damage the 
heater and void its warranty.