Electrical Installation -- Europe
230 Volt Electrical Installation
All 230V spas must be permanently connected (hardwired) to the power 
supply.  These  instructions  describe  the  only  acceptable  electrical  wiring 
procedure. Spas wired in any other way will void your warranty and may 
result in serious injury.
This is the only acceptable electrical wiring procedure. Spas wired in any 
other way will void your warranty. See the wiring diagram on page 15.
The electrical wiring of this spa must meet the requirements of any ap-
plicable local, state, and federal codes. The electrical 
circuit  must  be  installed  by  an  electrical  contractor 
and approved by a local building / electrical inspec-
tor.
RCD and Wiring Requirements
The power supplied to the spa must be on a dedi-
cated RCD protected circuit with no other appliances 
or lights sharing the power.
Use  copper  wire  with  THHN  insulation. Do  not  use 
aluminum wire.
Use  the  table  on  the  next  page  to  determine  your 
GFCI and wiring requirements.
When wires larger than #6 AWG are required, install a junction box near 
the spa and use #6 AWG wire between the junction box and the spa.
Wire runs over 85 feet must increase wire gauge to the next lower num-
ber. For example: A normal 50 amp RCD with four #8 AWG copper wires 
run over 85 feet would require you to go to four #6 AWG copper wires.
Testing the RCD Breaker
Test the RCD breaker prior to first use and periodically when the spa is 
powered. To test the RCD breaker follow these instructions (spa should 
be operating):
Press the TEST button on the RCD. The RCD will trip and the spa will 
1. 
shut off.
Reset the RCD breaker by switching the breaker to the full OFF posi-
2. 
tion, wait a moment, then turn the breaker back on. The spa should 
have power again.