42. Troubleshooting
TRO UBLE
PRO BABLE C AUS E
REMEDY
Ve n te r  m otor  wi l l  
n ot  start
1.  No power t o unit .
1. T urn on power, check supply fuses, or circuit  breaker. If unit  is equipped wit h 
unit -mount ed disconnect  swit ch, check circuit  breaker (See P aragraph 11).
2. No 24 volt  power t o vent er relay.
2. T urn up t hermost at ; check cont rol t ransformer out put . 
3. Vent er relay defect ive.
3. Replace relay. 
4. Defect ive mot or or capacit or.
4. Replace mot or or capacit or.  
Pi l ot  wi l l   n ot  l i gh t
1. Manual valve not  open.
1. Open manual valve.
(spark  i gn i ti on  
2. Air in gas line.
2. Bleed gas line.
syste m )
3. Dirt  in pilot  orifice.
3. Remove and clean wit h compressed air or solvent  (do not  ream). 
4. Gas pressure t oo high or t oo low.
4. Adjust  supply pressure. (See P aragraph 10). 
5.  Kinked pilot  t ubing.
5. Replace t ubing.
6.  P ilot  valve does not  open.
6. If 24 volt  available at  valve, replace valve. 
7. No spark:
7. 
a) Loose wire connect ions
a) Be cert ain all wires connect ions are solid.
b) T ransformer failure.
b) Be cert ain 24 volt s is available. 
c) Incorrect  spark gap.
c) Maint ain spark gap at  .100".
d) Spark cable short ed t o ground.
d) Replace worn or grounded spark cable. 
e ) Spark elect rode short ed t o ground.
e ) Replace pilot  if ceramic spark elect rode is cracked or grounded. 
f) Draft s affect ing pilot .
f) Make sure all panels are in place and t ight ly secured t o prevent   draft s at  pilot . 
g) Ignit ion cont rol not  grounded.
g) Make cert ain ignit ion cont rol is grounded t o furnace chassis
h ) Fault y ignit ion cont roller.
h )  If 24 volt  is available t o ignit ion cont roller and all ot her causes have been 
eliminat ed, replace ignit ion cont rol. 
8. Opt ional lockout  device int errupt ing cont rol 
circuit  by above causes.
8. Reset  lockout  by int errupt ing cont rol at  t hermost at .
9. Fault y combust ion air proving swit ch. 
9. Replace combust ion air proving swit ch. 
Pi l ot  l i gh ts,  m ai n      
1.  Manual valve not  open.
1. Open manual valve.
val ve   wi l l   n ot  ope n     2.  Main valve not  operat ing.
2.
(S park  Ign i ti on  
syste m )
a) Defect ive valve.
a) If 24 volt  is measured at  valve connect ions and valve remains closed, replace 
valve.
b) Loose wire connect ions.
b) Check and t ight en all wiring connect ions.
3. Ignit ion cont rol does not  power main  valve.  3.
a) Loose wire connect ions.
a) Check and t ight en all wiring connect ions.
b) Flame sensor grounded. (P ilot  light s - spark 
cont inues)
b) Be cert ain flame sensor lead is not  grounded or insulat ion or ceramic is not  
cracked. Replace as required.
c) Gas pressure incorrect .
c) Set  supply pressure at  5" w.c. t o 14" w.c. for nat ural gas and 11" w.c. t o 14" 
w.c. for propane gas. 
d) Cracked ceramic at  sensor.
d) Replace sensor.
e ) Fault y ignit ion cont roller.
e ) See P aragraph 33.  If all checks indicat e no ot her cause, replace ignit ion 
cont roller.  DO NOT  AT T EMP T  T O REP AIR IGNIT ION CONT ROLLER.  
T HIS DEVICE HAS NO FIELD REP LACEABLE P ART S.
No h e at (He ate r 
1. Incorrect  manifold pressure or orifices.
1. Check manifold pressure (See P aragraph 10).
O pe rati n g)
2. Cycling on limit  cont rol.
2. Check air t hroughput  (See P aragraph 15). 
3. Improper t hermost at  locat ion or adjust ment .  3. See t hermost at  manufact urer's inst ruct ions. 
C ol d  ai r  de l i ve re d
1. Fan cont rol improperly wired
1. Connect  as per wiring diagram.
  O n  S tart-u p
2. Defect ive fan cont rol.
2. Replace fan cont rol.
  Du ri n g O pe rati on
3. Incorrect  manifold pressure.
3. Check manifold line pressure (See P aragraph 10).
Motor  wi l l   n ot  ru n
1. Circuit  open.
1. Check wiring and connect ions. .
2. Fan cont rol inoperat ive.
2. Replace fan cont rol. 
3. Defect ive mot or or capacit or. 
3. Replace mot or or capacit or. 
Motor tu rn s on
1. Fan cont rol improperly wired.
1. Connect  as per wiring diagram.
an d off wh i l e  
2. Defect ive fan cont rol. 
2. Replace fan cont rol.
bu rn e r i s ope rati n g 
(S e e  m otor cu ts ou t 
3. P oor cont act  bet ween fan cont rol and heat  
exchanger t ube. Surface cont act  is required. 
3. Check for bent  mount ing or loose mount ing screws. 
on  ove rl oad 
4. Mot or overload device cycling on and off. 
4. Check mot or load against  mot or rat ing plat e.  Replace mot or if needed. 
be l ow)
5. Low ambient  t emperat ure (less t han 40
o
F) 
causing false cycling. 
5. Inst all fan delay relay kit  (See P aragraph 17.) 
Fan  m otor cu ts 
1. Low or high volt age supply .
1. Correct  elect ric supply.
ou t on  ove rl oad
2. Defect ive mot or.
2. Replace mot or. 
3. P oor air flow. 
3. Clean mot or, fan and fan guard. 
4. Defect ive bearing or lubricat ion. 
4. Lubricat e bearings or replace mot or. 
Bl owe r  m otor 
1. Improper mot or pulley and/or adjust ment . 
1. See inst ruct ions in P aragraph 14. 
cu ts ou t on  
2. Improper st at ic pressure in t he duct  syst em.
2. Adjust  duct  syst em dampers.
ove rl oad
3. Low volt age. 
3. Check power supply.