70 • 80 • 100 • 130 • 150 kW 
operating data
GENERATOR OUTPUT VOLTAGE/kW - 60Hz
kW LPG
Amp LPG
kW Nat. Gas
Amp Nat. Gas
CB Size (Both)
QT070
120/240 V, 1Ø, 1.0 pf
67
292
64
267
300
120/208 V, 3Ø, 0.8 pf
70
243
67
232
300
120/240 V, 3Ø, 0.8 pf
70
211
67
201
250
277/480 V, 3Ø, 0.8 pf
70
105
67
101
125
QT080
120/240 V, 1Ø, 1.0 pf
77
333
77
333
400
120/208 V, 3Ø, 0.8 pf
80
278
80
278
300
120/240 V, 3Ø, 0.8 pf
80
241
80
240
300
277/480 V, 3Ø, 0.8 pf
80
120
80
120
150
QT100
120/240 V, 1Ø, 1.0 pf
100
417
89
371
500
120/208 V, 3Ø, 0.8 pf
100
347
94
326
400
120/240 V, 3Ø, 0.8 pf
100
301
94
283
350
277/480 V, 3Ø, 0.8 pf
100
150
94
141
175
QT130
120/240 V, 1Ø, 1.0 pf
130
542
117
488
600
120/208 V, 3Ø, 0.8 pf
130
451
122
423
500
120/240 V, 3Ø, 0.8 pf
130
391
122
367
450
277/480 V, 3Ø, 0.8 pf
130
195
122
183
225
QT150
120/240 V, 1Ø, 1.0 pf
144
625
136
567
700
120/208 V, 3Ø, 0.8 pf
150
520
142
493
600
120/240 V, 3Ø, 0.8 pf
150
451
142
427
500
277/480 V, 3Ø, 0.8 pf
150
225
142
214
250
SURGE CAPACITY IN AMPS
Voltage Dip @ < .4 pf
15%
30%
QT070
120/240 V, 1Ø
129
356
120/208 V, 3Ø
194
471
120/240 V, 3Ø
168
408
277/480 V, 3Ø
83
201
QT080
120/240 V, 1Ø
174
435
120/208 V, 3Ø
186
466
120/240 V, 3Ø
161
404
277/480 V, 3Ø
70
175
QT100
120/240 V, 1Ø
150
413
120/208 V, 3Ø
186
452
120/240 V, 3Ø
161
392
277/480 V, 3Ø
107
261
QT130
120/240 V, 1Ø
236
648
120/208 V, 3Ø
364
885
120/240 V, 3Ø
315
767
277/480 V, 3Ø
161
390
QT150
120/240 V, 1Ø
486
1214
120/208 V, 3Ø
534
1334
120/240 V, 3Ø
463
1156
277/480 V, 3Ø
250
624
Standby Generators
ENGINE FUEL CONSUMPTION
Natural Gas
Propane
(ft³/hr)
(m³/hr)
(gal/hr)
(l/hr)
QT070
Exercise cycle
110
3.1
1.2
4.6
25% of rated load
260
7.4
2.85
10.8
50% of rated load
500
14.2
5.46
20.8
75% of rated load
696
19.8
7.62
29.1
100% of rated load
1020
29
11.17
42.6
QT080
Exercise cycle
131
3.7
1.45
5.5
25% of rated load
312
8.9
3.45
13.1
50% of rated load
600
17.1
6.64
25
75% of rated load
835
23.7
9.25
34.9
100% of rated load
1154
32.8
12.78
48.2
QT100
Exercise cycle
130
3.7
1.4
5.4
25% of rated load
371
10.5
4.1
15.5
50% of rated load
713
20.3
7.9
29.8
75% of rated load
991
28.2
11
41.5
100% of rated load
1260
35.8
13.9
52.6
QT130
Exercise cycle
135
3.8
1.4
5.7
25% of rated load
482
13.7
5.3
20
50% of rated load
927
26.3
10.3
38.7
75% of rated load
1292
36.7
14.3
54
100% of rated load
1786
50.8
19.8
74.6
QT150
Exercise cycle
155
4.4
1.7
6.5
25% of rated load
556
15.8
6.09
23.2
50% of rated load
1070
30.4
11.72
44.7
75% of rated load
1491
42.4
16.33
62.3
100% of rated load
2061
58.6
22.57
86.1
STANDBY RATING: Standby ratings apply to installations served by a reliable utility source. The standby rating is applicable to varying loads for the duration of a power outage.  There 
is no overload capability for this rating. Ratings are in accordance with ISO-3046-1. Design and specifications are subject to change without notice.
Note: Fuel pipe must be sized for full load. 
For Btu content, multiply ft
3
/hr x 2520 (LP) or ft
3
/hr x 1000 (NG).
For megajoule content, multiple m³/hr x 93.89 (LP) or m³/hr x 37.26 (NG).
Refer to "Emissions Data Sheets" for maximum fuel flow for EPA and SCAQMD permitting purposes.