5 - 48 
MELSEC-Q
 
5   DATA USED FOR POSITIONING CONTROL 
 
2)   When the difference between the last command position of the 
QD75MH at the time the servo stop signal turned ON and the 
present value at the time the servo stop signal turned OFF is greater 
than the value set in the buffer memory for the restart allowable 
range setting, the positioning operation is judged as on-standby and 
cannot be restarted.  
 
ON
OFF
Operation
Error
Servo OFF
Stopping/Waitting
Last command position
Servo ON
Restart invalid
Restart valid
Axis status
Servo emergency
stop signal
 
 
(b)   Processing when the servo ON signal changes from OFF to ON. 
1)   The positioning operation is stopped and restart can be performed 
when the difference between the last command position of the 
QD75MH when the servo ON signal went from OFF to ON is lower 
than the value set in the buffer memory for restart allowable range 
setting. 
2)   When the difference between the last command position of the 
QD75MH at the time the servo ON signal when from ON to OFF and 
the present value at the time the servo ON signal went from OFF to 
ON is greater than the value set in the buffer memory for the restart 
allowable range setting, the positioning operation is judged as on-
standby and cannot be restarted. 
 
Axis status
Servo emergency 
stop signal 
Stopping
Positioning
Servo OFF
Stopping/Waiting
Stop command
Servo OFF
Waitting
Restart invalid
Restart valid
Servo ON
ON
OFF
Servo ON
Restart invalid
 
 
(2)   Setting method 
When performing restart at the time servo OFF changes to ON, set the restart 
allowable range in the following buffer memory. 
 
Setting value buffer memory 
address 
Axis 1  Axis 2  Axis 3  Axis 4 
Item Setting 
range 
Default value 
64 
65 
214 
215 
364 
365 
514 
515 
 Pr.84 
 Restart allowable range 
setting when servo OFF 
changes to ON 
0, 1 to 327680 (PLS) 
0: restart not allowed 
 
[Setting example] 
A program in which the restart allowable range for axis 1 is set to 10000 PLS 
is shown below. 
 
DMOVP K10000 D0
DTOP  H0  K64  D0  K1
Restart allowable range (10000 PLS)
is stored in D0, D1.
Data for D0, D1 is stored in buffer
memory 64, 65 of the QD75MH.