The BC1524 and BC3012 range provides fully automatic, 
heavy duty charging of vented lead acid or NiCd batteries. 
The chargers may be used in a wide range of industrial 
battery applications, including standby engines, pumps 
and generators. 
The charger uses an open frame construction, designed  
for surface mounting in an enclosed panel. Each unit 
consists of a transformer, rectifier and control circuit.  
The control circuit ensures that charger maintains the 
battery voltage at the pre-calibrated float level, while 
supplying any additional load current up to the specified 
maximum. 
A ‘boost’ operating mode can be used to provide increased 
voltage output. Selection of normal or boost mode is via 
three terminals, allowing activation by a remote panel 
switch or time relay – see calibration table overleaf for  
float and boost voltage levels. 
A self diagnostic ‘charge fail’ circuit and relay output is  
provided as standard. The volt free relay de-energises  
in the event of a charging fault. 
Power for the charger is from a 230VAC or 110VAC  
supply (please specify at order). All electrical connections 
are to stripped panel wiring via spring-loaded clamp 
terminals. 
 
Warranty 
A one year limited warranty on materials and workmanship 
is given with this Murphy product. Details are available on 
request and at www.fwmurphy.co.uk/warranty
BC1524 and BC3012
Automatic Battery Chargers 
ys6307
revision A, 21
st
  October 2004
catalogue section 40
Product specification 
power supply:
BC1524 
BC3012 
nominal operating voltages 
permissible voltage variation 
nominal operating frequency 
230 VAC or 110 VAC (specify) 
 ± 10% of nominal 
50/60 Hz. 
DC charge output: 
 
maximum current, A DC 
15 
30 
nominal voltage, V DC 
24 
12 
float/boost voltages 
see table overleaf 
charge fail output:
 
relay type 
 
contact rating 
volt free SPDT contacts, relay 
de-energised on fault 
1A @ 30 VDC (resistive load) 
general:
 
operating temperature 
–10 to +55 
o
overall dimensions (w x h x d) 
185 x 175 x 135 mm 
weight 
approx. 7.8 Kg 
Heavy duty float charging:
 
15A (24V) or 30A (12V) output 
 
Simple, low cost design 
 
Lead acid or Ni-Cd calibrations
 
Float or boost modes 
 
Charge fail relay output 
 
 
 
 
 
 
FW Murphy 
PO Box 470248 
Tulsa, Oklahoma 74147, USA 
tel:  +1 918 317 4100 
fax:  +1 918 317 4266 
email: sales@fwmurphy.com 
web: www.fwmurphy.com
 
CONTROL SYSTEMS AND SERVICES DIVISION 
PO Box 1819, Rosenberg, Texas 77471, USA 
tel: +1 281 633 4500 
fax: +1 281 633 4588 
email: sales@fwmurphy.com 
MURPHY DE MEXICO S.A. DE C.V. 
Blvd. Antonio Rocha Cordero 300, Fracción del Aguaje 
San Luis Potosí, S.L.P. México 78384 
tel: +52 444 8206264 
fax: +52 444 8206336 
Villahermosa office tel: +52 993 3162117 
email: ventasmex@murphymex.com.mx 
web: www.murphymex.com.mx 
FRANK W. MURPHY LTD. 
Church Rd, Laverstock, Salisbury, SP1 1QZ, UK 
tel: +44 1722 410055 
fax: +44 1722 410088 
email: sales@fwmurphy.co.uk 
web: www.fwmurphy.co.uk 
MURPHY SWITCH OF CALIFORNIA 
41343 12th Street West, 
Palmdale, CA 93551-1442, USA 
tel: +1 661 272 4700 
fax: +1 661 947 7570 
email: sales@murphyswitch.com 
web: www.murphyswitch.com 
MACQUARRIE CORPORATION 
1620 Hume Highway, 
Campbellfield, Victoria 3061, Australia 
tel: +61 3 9358 5555 
fax: +61 3 9358 5558 
email: murphy@macquarrie.com.au 
 
In order to consistently bring you the highest quality, full featured products, we reserve the right to change our specifications and designs at any time.