D400 Substation Data Manager User's Manual  
33
 
 
Switch SW3/SW4 Configuration 
Switches SW3 (for Channel 2 on TB1-6 through TB1-10) and SW4 (for Channel 1 on TB1-1 
through TB1-5) contain ten DIP-switches that control pull-up and pull-down resistors for 
the differential data lines and provide line termination between the differential data pairs. 
Each DIP-switch can be set to ON or OFF to select the appropriate function for the switch. 
That is, if all pins are set to ON, switch is ON. If all pins are set to OFF, switch is OFF. 
If termination/pull up is selected, the TX+ and RX+ signals have a 680 ohm pull-up 
resistor, the TX- and RX- signals have a 680 ohm pull-down resistor, and the RX and TX 
signals have a 120 ohm termination. 
 
RS-485 Card Switch SW3/SW4 Settings 
SW3/SW4 Pin  Pin Position Function 
ON Pull-up 
for 
TX+ 
OFF 
No pull-up for TX+ 
ON 
Pull-down for TX- 
OFF 
No pull-down for TX- 
3 Not 
connected 
ON Pull-up 
for 
RX+ 
OFF 
No pull-up for RX+ 
ON 
Pull-down for RX- 
OFF 
No pull-down for RX- 
ON 
Line termination between TX+ and TX-  
OFF 
No Line termination between TX+ and TX- 
ON 
Line termination between TX+ and TX-  
OFF 
No Line termination between TX+ and TX- 
8 Not 
connected 
ON 
Line termination between RX+ and RX-  
OFF 
No Line termination between RX+ and RX- 
ON 
Line termination between RX+ and RX-  
10 
OFF 
No Line termination between RX+ and RX-