994-0089–1.00–2, General
 
 
Power Fail Alarm Connection 
Station Battery / Power Source
Light ON when
operational
Light ON after
failure
 
System Fail  
The D400 includes a System Fail contact closure to provide an external LED indication on 
the system or LAN status.  
The LED notification can be wired to operate as follows: 
•  ON when system is functioning properly 
•  ON when system failure has occurred 
The System Fail contact closure provides three contacts (terminals 4, 5 and 6) on terminal 
block TB2
 
Caution: 
Contact closure rated for 0.1 A @ 300 V maximum. 
» 
To connect the System Fail relay: 
1. 
Remove the terminal block protective plastic cover. 
2. 
Wire a lamp to terminals 4, 5 and 6 on terminal block TB2 as follows: 
To enable the indicator when power is… 
Wire the lamp between… 
Functioning properly  
Terminals 4 and 5 
Failed 
Terminals 5 and 6 
For proper connection, the recommended tool torque settings for power terminal 
screws are 10.8 in-lb [1.22 Nm]. 
3. 
Replace the terminal block protective plastic cover. 
!