Smart-UPS 750/1000/1500/2200/3000 VA  100/120/230 Vac / 500 VA 100 Vac  Tower
Low Transfer Point
100 Vac:
92 Vac
86 Vac - 92 Vac
Set the transfer point lower if the utility voltage is 
chronically low and the connected equipment can 
tolerate this condition.This setting may also be adjusted 
using the power quality setting.
Note: Use the Advanced Menus to configure this 
setting.
120 Vac: 
106 Vac
97 Vac - 106 Vac
230 Vac:
208 Vac
196 Vac -208 Vac
Nominal Output 
Voltage
100 Vac
N/A
230 Vac models only: Set the nominal output voltage of 
the UPS to standby mode. 
120 Vac
N/A
230 Vac
• 220 Vac
• 230 Vac
• 240 Vac
Transfer Sensitivity
Normal
Normal, Reduced, Low
Select the level of sensitivity to power events that the 
UPS will tolerate.
• Normal: The UPS will go on battery power more 
often to provide the cleanest power supply to the 
connected equipment.
• Low: The UPS will tolerate more fluctuations in 
power and will go on battery power less often. 
If the connected load is sensitive to power disturbances, 
set the sensitivity to Normal.
Low Battery Warning 120 sec
Set the value in seconds
The UPS will emit an audible alarm when the remaining 
runtime has reached this level.
Date of Last Battery 
Replacement
Date set at factory
Reset this date when the battery module is replaced.
Audible Alarm
On
On/Off
The UPS will mute all audible alarms if this is set to Off 
or when the display keys are pressed.
Battery 
Self-Test Interval 
Setting
On start up and every 
14 days since the last 
test
• Never
• Start up only
• Frequency of test 
(every 7 to 14 days)
The interval at which the UPS will execute a 
self-test.
Reset to Factory 
Default
No
Yes/No
Restore the UPS factory default settings.
Function
Factory Default
Options
Description