APC 66124 User Manual

Page of 4
3402231500/AC
  
The Network Management Teleservice Card (66124) is 
recommended for central UPSs protecting entire networks or for UPS 
units backing up critical loads.
With the card installed, the UPS has its own IP address and uses the 
local computer capabilities to:
◗  supply web pages (http or https (SSL)) with information on status 
conditions and measurements/settings/alarms,
◗  integrate an SNMP-based NMS such as HP OpenView, IBM Tivoli 
Netview and Computer Associates Unicenter,
◗  communicate with shutdown modules installed on the protected 
servers (Network Shutdown Module),
◗  send e-mail and SMS messages,
◗  control the ON/OFF function of the UPS and the outlets,
◗  monitor the Environment Sensor,
◗  Access the Teleservice solution for remote monitoring and 
maintenance services of your UPS.
  
◗  One Network Management Teleservice Card (66124),
◗  One serial cable for configuration (3402226700),
◗  One phone cable for teleservice (3402226800),
◗  One installation manual (34022315EN),
◗  One Teleservice information form (3402228500),   
  
      
  
PHONE port  
ETHERNET port  
Service port (Sensor/RS485)   
Default settings, sensor configuration : 
INTRODUCTION
 
The Network Management Teleservice Card  must be  
installed and used in accordance with manufacturer 
instructions.
UNPACKING AND CHECKS
 
Installation manual
Network
Management
Teleservice Card
(66124)
66108
Settings/Sensor
ETHERNET
UPS dat
a    RS232
100M
           10M
Settings/Sensor
Settings/Sensor
Settings/Sensor
Settings/Sensor
66124
Settings/Sen
sor
ETHERNE
T
UPS data    R
S232
100M           1
0M
Settings/Sen
sor
Settings/Sen
sor
Settings/Sen
sor
Settings/Sen
sor
OVERVIEW
 
INDICATIONS
LED
Colour
Status
Description
UPS Data
Green
◗  
OFF
◗  
ON
◗  
Flashing
◗  
Card not connected to phone 
network
◗  
Card connected to phone 
network, but no activity
◗  
Port is sending/receiving
CD
Orange
◗  
OFF
◗  
ON
◗  
Flashing
◗  
Modem is not connected
◗  
Modem is connected
◗  
Modem is connecting
LED
Colour
Status
Description
ACT
Green
◗  
OFF
◗  
ON
◗  
Flashing
◗  
Card not connected to network
◗  
Card connected to network, but 
no activity
◗  
Port is sending/receiving
100M
Orange
◗  
OFF
◗  
ON
◗  
Port operating at 10 Mbits/s
◗  
Port operating at 100 Mbits/s
LED
Colour
Status
Description
Sensor
Green
◗  
OFF
◗  
ON
◗  
Flashing
◗  
Card starting
◗  
Card ready
◗  
Communication with environment 
Sensor is operational
RS485
Orange
◗  
OFF
◗  
Flashing
◗  
Flashing 
every seconds
◗  
Settings mode activated
◗   
Port is sending/receiving
◗  
Communication fault or 
configuration errors
SWITCHES SETTING
 
 
 
 
 
 
 
 
MAC adress
PHONE port: 
Green LED : Phone communication 
with the UPS
Orange LED : Modem connection
ETHERNET port: 
Green LED : Connection + activity
Orange LED : 10/100 M
Service port (Sensor/RS485):
Green LED : Communication with 
the UPS
Orange LED :RS232 activity
 
Catalogue number
66124
SENSOR/RS 485
ETHERNET
( Settings)
100M
UPS Dat
a         CD
PHONE
RESET
ACT
000623001C07
000623001C07
SA2
1
8
3
SA1
1
8
3
OFF
ON
OFF
ON