APC AP9606 User Manual

Page of 84
Web/SNMP Management SmartSlot Card User’s Guide
61
Management Card and Device Events
Overview
The Management Card, UPS, and Environmental Monitoring SmartSlot 
Card all generate event codes in response to specific conditions. Each 
event has a unique code and is classified as having no severity level, or 
with a default severity level that indicates the seriousness of the event.
Note:
For information about severity levels and how they define the 
actions associated with an event, se
.
Management Card 
events
The following table identifies the Management Card events (labeled as 
System events in the table’s descriptions).
Note:
The Management Card has events that are classified as having 
no severity level. You cannot configure any action to occur for 
such events.
Continued on next page
Code
Severity
Description
0x0001
Severe
System: Coldstart. (The Management Card was turned on.)
0x0002
Severe
System: Warmstart. (The Management Card was reset 
while it was turned on.)
0x0003
Warning
System: SNMP configuration change.
0x0004
Informational
System: Detected an unauthorized user attempting to 
access the SNMP interface.
0x0005
Warning
System: Detected an unauthorized user attempting to 
access the Control Console interface.
0x0006
Warning
System: Detected an unauthorized user attempting to 
access the Web interface.
0x0008
Warning
System: Password changed.
0x000C
No severity
System: File transfer started. (FTP)
0x000D
No severity
System: File transfer started. (TFTP) 
0x000F
No severity
System: File transfer failed. 
0x0014
No severity
System: Control Console User logged in. 
0x0015
No severity
System: Web User logged in. 
0x0016
No severity
System: FTP User logged in. 
0x0018
No severity
System: Reset to Defaults. 
0x0019
No severity
System: Initializing data.