APC Command Line Interface User Manual

Page of 39
Command Reference: Outlet Commands
20
Command Line Interface (CLI) User’s Guide
reboot
Syntax: 
                 all
reboot       outlet|range[,outlet|range...]
           
                                                       
Description: 
Remove and then restore power to 
one or more outlets. The CLI does not wait for the 
reboot command to complete before providing 
output and re-displaying the CLI prompt (APC> ). 
If you specify more than one outlet, the outlets will 
turn off and on approximately at the same time. 
However, for close synchronization, outlets must 
be configured as part of a synchronized outlet 
group.
Parameters: 
Example: 
reboot 1,5-7
Output Format (for the preceding example): 
OK
1: Database Server: Outlet rebooting.
5: Disk Array PS 1: Outlet rebooting.
6: Disk Array PS 2: Outlet rebooting.
7: Disk Array PS 3: Outlet rebooting.
Example: 
reboot “Web Server”
Output Format (for the preceding example): 
OK
2: Web Server: Outlet rebooting.
3: Web Server: Outlet rebooting.
Error Messages: 
E101, E104
all
The value all removes and then restores power 
to all outlets of the Switched Rack PDU. This 
value is not case-sensitive.
outlet  An outlet name or number. If you specify a 
name that contains a Space character, you 
must enclose the name in quotation marks
range  A range of outlet numbers, with a hyphen 
separating the starting number from the 
ending number.