Omron CJ1W-EIP21 User Manual

Page of 464
211
Using FINS Applications
Section 8-5
8-5
Using FINS Applications
8-5-1
CX-Programmer (CX-Server)
The following examples show how to connect online from a CX-Programmer
on an Ethernet network to a PLC on the Ethernet network.
System Configuration Example 1: No Routing
In this example, an online connection is made by FINS/UDP to a PLC on an
Ethernet network (PLC1 in the diagram below) from a CX-Programmer/CX-
Integrator connected to the Ethernet network.
Conditions
• FINS/UDP method
• IP Address Conversion: Automatic (Dynamic) generation method
CX-Programmer's Change PLC Dialog Box 
CX-Programmer's FINS/UDP Tab Page in Edit Parameters Dialog Box
CX-Programmer/CX-Integrator
Ethernet or EtherNet/IP (Network address: None)
Ethernet port
Target: PLC1
EtherNet/IP Unit
IP address: 192.168.250.1
FINS/UDP method
Node number: 1
IP address conversion: Automatic 
generation method (dynamic)
EtherNet/IP Unit node number: 2
EtherNet/IP Unit IP address: 192.168.250.2
Settings for target PLC (PLC1)'s Change PLC Dialog Box
Setting
PLC name
PLC1
Network classification
Ethernet
Network Tab Page
FINS transmission source address
0
FINS destination
Network number
0
Node address
2
Frame length
2,000 bytes
Response monitor time
2 seconds
Driver Tab Page
Workstation node address
1
Automatic generation method
Not selected
IP address
192.168.250.2 (Eth-
erNet/IP Unit or 
built-in EtherNet/IP 
port IP address)
Port number
9600
Item
Setting
FINS/UDP Port
Default (9600)
IP Address Conversion
Automatic (Dynamic) generation method
IP Router Table
None