Omron CJ1W-EIP21 User Manual

Page of 464
393
FINS Commands Addressed to EtherNet/IP Units or Built-in EtherNet/IP Ports
Appendix E
Mode Setting (Response)
The mode setting in the system setup is returned.
Broadcast Address Setting
Communications Partner IP Address Conversion Method Setting
FINS/UDP Port Number Setting
FINS/TCP Port Number Setting
Baud Rate Setting
SNTP Server Specification Method
Ethernet Address (Response)
The Ethernet address of the EtherNet/IP Unit or built-in EtherNet/IP port is returned.
Note This Ethernet address is listed on the label on the side of the EtherNet/IP Unit or (for a built-in EtherNet/
IP port), on the CPU Unit.
Bit 1: Broadcast setting 
Bit 4: UDP port number setting for FINS
Bits 2 and 3: IP address conversion method 
6
8
10 
11 
12 
13
14 
15 
Bit 5: TCP port number setting for FINS/TCP
Bit 8: Transmission speed (baud rate) 
Bit 9: SNTP server specification method
Bit 1
Meaning
0
Broadcast with host number set to all ones (4.3BSD specifications)
1
Broadcast with host number set to all zeroes (4.2BSD specifications)
Bit 3
Bit 2
Meaning
0
0
Automatic generation method (dynamic)
0
1
Automatic generation method (static)
1
0
IP address table reference method
1
1
Combined method (IP address table reference + automatic generation 
(dynamic))
Bit 4
Meaning
0
Default (9600)
1
Unit Setup value
Bit 5
Meaning
0
Default (9600)
1
Unit Setup value
Bit 8
Meaning
0
Automatic detection
1
Fixed
Bit 9
Meaning
0
IP address
1
Host  name