Omron CJ1W-EIP21 User Manual

Page of 464
17
EtherNet/IP Unit and Built-in EtherNet/IP Port Specifications
Section 2-1
2-1-3
Communications Specifications
Item
CS1/CJ1
CJ2H
CJ2M
CIP 
service
Tag data 
links 
(Cyclic 
communi-
cations)
Number of connections 256
32
Packet interval (refresh 
cycle)
0.5 to 10,000 ms (in 0.5-ms units)
Can be set independently for each connection. 
(Data is refreshed over the network at the preset 
interval and does not depend on the number of 
nodes.)
1 to 10,000 ms (in 0.5-
ms units)
Can be set indepen-
dently for each connec-
tion. 
(Data is refreshed over 
the network at the pre-
set interval and does 
not depend on the 
number of nodes.)
Allowed communica-
tions bandwidth per 
Unit
6000 pps (See note 1.)
Note Including the heartbeat. 
3000 pps (See note 1.)
Note Including the 
heartbeat. 
Number of tags that 
can be registered
256
32
Tag types
CIO Area, DM Area, EM Area, Holding Area, Work Area, and network 
symbols (See note 8.)
Number of tags per 
connection (= 1 tag 
set)
8 (7 tags when the tag set contains the PLC status)
Maximum link data size 
per node
184,832 words
640 words
Maximum data size per 
connection
252 words or 722 words (See note 2.)
Note Data synchronicity is maintained within 
each connection.
20 words
Note Data synchronic-
ity is maintained 
within each con-
nection.
Number of registrable 
tag sets
256
(1 connection = 1 tag set)
32
(1 connection = 1 tag 
set)
Maximum size of 1 tag 
set
722 words
(The PLC status uses 1 word when the tag set 
contains the PLC status.)
20 words
(The PLC status uses 1 
word when the tag set 
contains the PLC sta-
tus.)
Maximum number of 
tags that can be 
refreshed per CPU Unit 
cycle (See note 3.)
Output/Transmission 
(CPU 
 EtherNet/IP): 
19
Input/Reception 
(EtherNet/IP 
 CPU): 
20 (See note 4.)
Output/Transmission 
(CPU 
 EtherNet/IP): 
256
Input/Reception 
(EtherNet/IP 
 CPU): 
256
Output/Transmission 
(CPU 
 EtherNet/IP): 
32
Input/Reception 
(EtherNet/IP 
 CPU): 
32
Data that can be 
refreshed per CPU Unit 
cycle (See note 3.)
Output/Transmission 
(CPU 
 EtherNet/IP): 
7,405 words
Input/Reception 
(EtherNet/IP 
 CPU): 
7,405 words
Output/Transmission 
(CPU 
 EtherNet/IP): 
6,432 words
Input/Reception 
(EtherNet/IP 
 CPU): 
6,432 words
Output/Transmission 
(CPU 
 EtherNet/IP): 
640 words
Input/Reception 
(EtherNet/IP 
 CPU): 
640 words
Changing tag data link 
parameters during 
operation
Supported (See note 5.)
Multicast packet filter 
function (See note 6.)
Supported