Omron CJ1W-EIP21 User Manual
58
Tag Data Link Parameters
Section 3-9
The following method can be used to easily set the data links shown in the fol-
lowing figure using a wizard in the EtherNet/IP Datalink Tool.
lowing figure using a wizard in the EtherNet/IP Datalink Tool.
1,2,3...
1.
Start the Network Configurator, select the applicable EtherNet/IP Unit in
the Tree View on the left, and then paste it into the Device Configuration
Pane on the right.
the Tree View on the left, and then paste it into the Device Configuration
Pane on the right.
Note If an EtherNet/IP system has already been installed, you can create a similar
device configuration by connecting to the EtherNet/IP network and selecting
Network
Network
−
Upload from the menus.
Refer to
for infor-
mation on connecting.
2.
Select Network
−
EtherNet/IP Datalink Tool from the menus to start the
EtherNet/IP Datalink Tool.
#1
#2
#3
#1
#2
#3
#3
#1
#2
#3
#1
#2
#2
#1
#3
#2
#1
#3
EtherNet/IP
W0
W0
D50 D50
Node #1: CJ1H-CPU67H
(IP address: 192.168.250.1)
Node #2: CJ1H-CPU67H
(IP address: 192.168.250.2)
Node #3: CJ1H-CPU67H
(IP address: 192.168.250.3)
Area 1
W0
50 words
W50
50 words
W100
50 words
Area 2
D50
100 words
D150
100 words
D250
100 words