Liebert EM User Manual

Page of 48
Web Interface Overview
12
4.2
Tabs
The tabs at the top right of the Web interface window provide access to all the functions of the 
OpenComms EM device. Table 5 summarizes these functions and where to find more information.
4.3
Color-Coded Status
The Web interface uses color coding to indicate the status of sensors connected to the unit, as shown 
in Table 6to help you quickly identify sensors that require attention.
In EM PDU and vEM-14 controllers, the same color scheme is used for MP Advanced Power Strips 
connected to the unit.
These colors are used to display the sensor’s name, the current reading and the status of the sensor; 
the colors are also used in line graphs to indicate alarm thresholds. 
Table 5
Summary of tab functions
Tab
Display
Additional
Links
Description
For details, see:
Summary
Summary
window
View current value & status of all 
connected devices
Sensors
Sensors
window
Data
View all data for connected devices
Names
Change names of connected 
devices
Graph
Display data in graph format
Power
(EM PDU & 
vEM-14 
controllers)
Power
window
View and set up MP Advanced 
Power Strips
Alerts
Alerts
window
Email
Activate and configure automatic 
e-mail alerts
Modem
Activate and configure automatic 
pager alerts
SNMP Traps
Activate and configure automatic 
SNMP trap alerts
Security
Security
window
Change password to Web interface; 
set up additional users, type of 
access, timeout after inactivity
Sys Info
Sys Info
window
Network
Connectivity
Configure network settings
SNMP
Information
Configure unit for SNMP
Data
Presentation
Change time intervals for updating 
sensor data, Web page refresh; 
change temperature units (°F / °C)
Serial Ports
(not used)
View or change settings for serial 
ports 1 and 2
Table 6
Color coding used in Web interface
Display Color
Meaning
Sensor 
Name
Status &
Current Value
Graph
Line Color
Red
Red
Red
Critical state (High Critical, Low Critical, Critical)
Yellow
Yellow
Yellow
Warning state (High Warning, Low Warning)
Green
Green
Normal
Gray
Black
Not present (not connected to unit)