5
3.2.1 Data Overview—XDK
Table 2
Technical data
Housing material
Aluminium sheet, sheet steel, galvanized  and coated
Operating Temperature range
50°F to 95°F (10°C to 35°C)
Abs. atmospheric humidity
8g / kg maximum
Temperature difference across server
approx. 15K
Noise level
55 dB(A) sound pressure at a distance of 3 ft. (1m)
Useful load
2204 lb (1000kg)
Cold Water
Cooling capacity
17kW
Supply temperature
54°F (12°C) (other temperatures upon consultation)
Return temperature
64°F to 72°F (18°C to 22°C)  (other temperatures upon consultation)
Max. operating pressure
145 PSI (10 bar)
Water supply connection
1"
Table 3
XDK general data
Nominal Cooling Capacity
17kW @ 54°F (12°C) EFT
Height, in (mm)
86.6 (2200)
Width, in (mm)
31.5 (800)
Depth, in (mm)
47 (1200)
Usable Height for Electronic
Equipment
40 U
Maximum Electronic
Equipment Depth, in (mm)
29 (740)
Electronic Equipment
Air Temperature, In/Out, °F (°C)
68/98 (20/37
Weight, Empty, lb (kg)
683 (310)
Maximum Weight, Filled 
2,800 (1310)
Maximum Operating
Water Pressure, psi (bar)
145 (10)
Water Flow Rate, GPM (m
3
/h)
 10.7 (2.44)
Water Pressure Drop, psi (bar)
10 (0.7)
Water Connections, in
1
Maximum Air Flow, CFM ( m
3
/h)
1800 (3,100)
Sound Pressure Level
 55 dB(A) at 3 ft (1m)
Input Voltage
200-264 V, 1 ph, 50/60 Hz
Maximum Power Draw
1400W
Options
Leveling Feet or Casters