Diagnostics and Troubleshooting - User Interface 
Revision 5 
  HC900 Hybrid Controller Installation and User Guide 
125 
9/03  
Table 27 - Controller Module Diagnostics 
OI Screen 
Item  
OI Screen 
Item Value 
Number of 
LED 
Strobes  
Possible Cause 
Control File Action 
User Action 
IO RACK 
COMM FAIL 
The Main CPU is 
unable to successfully 
communicate to an 
expansion rack(C50 
CPU only) that is in its 
configuration. 
See RACK BACKPLANE 
FAIL. 
1. Verify that the 
expansion rack 
should be in the 
configuration 
2. Verify that the 
jumpers on the 
scanner are set up 
for the correct rack 
address. 
3. Check that 
expansion rack is on. 
4. Check the expansion 
rack’s status LED for 
diagnostic 
information. 
5. Check that cable is 
connected to 
expansion rack. 
6. If a hub is used, 
check that all cables 
are properly 
connected to the 
hub, proper 
crossover cables are 
used, and that hub is 
powered. 
7. Cycle power to the 
rack. 
8. Cycle power to the 
hub. 
9. Replace the 
expansion rack’s 
power supply. 
10. Replace the 
expansion rack. 
11. Replace the 
expansion rack’s 
scanner board. 
12. Replace the main 
CPU. 
 RACK 
SW 
INCOMPATILITY 
The Main CPU 
determined that its 
software is not 
compatible with the 
scanner module. 
All associated module 
diagnostics are set to 
MODULE NO COMM. 
 
Refer to MODULE NO 
COMM diagnostic for 
further details. 
 
1. Upgrade the scanner 
software either by 
replacing the module 
or doing a code-
download. 
2. Update Main CPU 
software either by 
replacing the module 
or doing a code 
download.