Honeywell HC900 User Manual

Page of 228
Diagnostics and Troubleshooting - User Interface 
130 
  HC900 Hybrid Controller Installation and User Guide 
Revision 5 
  
9/03 
Table 27 - Controller Module Diagnostics 
OI Screen 
Item  
OI Screen 
Item Value 
Number of 
LED 
Strobes  
Possible Cause 
Control File Action 
User Action 
RS-232 GOOD  N/A  N/A 
N/A 
N/A 
 DATA 
LINK 
FAILURE 
A large number of 
messages are 
resulting in data link 
errors. 
1. Rack 1 monitor block’s 
COMPORT DIAG is set 
to FAILED. 
2. Rack 1 monitor block’s 
RACK OK pin is turned 
off. 
3. ASYS block’s HW OK 
pin is turned off. 
4. If configured as a 
Modbus master:  
1.  ASYS and FSYS 
blocks’ Modbus Master 
Fail pins are turned on. 
2.  Slave and read blocks 
associated with the 
slaves experiencing the 
failure have their read 
pins frozen to the last 
value read. 
3.  Slave blocks associated 
with the slaves 
experiencing the failure 
have their BAD COMM 
and NO SCAN pins 
turned on. 
4.  IN SCAN STATUS is 
set to NO for all slaves 
experiencing the failure. 
5.  COMM STATUS is set 
to BAD for all slaves 
experiencing the failure. 
6.  The slaves with the data 
link errors have a non-
zero data link error 
count. 
7. The slaves experiencing 
the failure are moved to 
the background scan 
rate.
 
1. Check baud rate 
2. Check connectors 
3. Check cable polarity 
4. Isolate cabling from 
electrical 
interference 
5. If RS232 to RS485 
converter is used, 
check its power, 
switch/jumper 
settings, and polarity. 
6. If configured as a 
Modbus master, use 
the slave status 
screens to determine 
which slaves are 
experiencing the 
problem. For those 
slaves check: 
• power 
• connections 
• address 
 baud rate 
• parity 
• number of stop bits 
• for electrical 
interference 
• grounding 
• termination resistor (if 
at end of link) 
7. The diagnostic is 
cleared by clearing 
the port’s statistics.