Honeywell HC900 User Manual

Page of 228
Specifications - HC900 Hybrid Controller Design 
156 
  HC900 Hybrid Controller Installation and User Guide 
Revision 5 
  
9/03 
Specifications 
HC900 Hybrid Controller Design 
 
Controller Module 
Feature 
Description 
CE Conformity (Europe) 
This product is in conformity with the protection requirements of the following 
European Council Directives: 73/23/EEC, the Low Voltage Directive, and 89/336/EEC, 
the EMC Directive. Conformity of this product with any other “CE Mark” Directive(s) 
shall not be assumed. EN61326: Electrical Equipment For Measurement, Control and 
Laboratory use. EMC requirements. 
Installation Category 
(Over-voltage Category) 
Category II: Energy-consuming equipment supplied from the fixed installation 
(Multi-loop Process Controller). Local level appliances, and Industrial Control 
Equipment. (EN 61010-1) 
Pollution Degree 
Pollution Degree 2: Normally non-conductive pollution with occasional conductivity 
caused by condensation. (ref. IEC 664-1) 
EMC Classification 
Group 1, Class A, ISM Equipment  
Product Classification 
Class I: Fixed, Permanently Connected, Industrial Process Control Equipment with 
protective earthing (grounding). (EN 61010-1) 
Power, per rack 
Controller Rack 
 
 
Voltage:  Universal power, 90 to 264 Vac, 47 to 63Hz 
Rating: 130VA @ 264VAC, typical 110VA @ 115VAC 
In-rush current: 7 amps peak-to-peak for 150 ms at 240 Vac 
Variable; depends on I/O Module complement.