Specifications - Analog Input, Analog Output Modules: Common Features 
Revision 5 
  HC900 Hybrid Controller Installation and User Guide 
161 
9/03  
Analog Input, Analog Output Modules: Common Features 
 
Feature Description 
Micro Controller 
Motorola 68HC11 micro controller 
12k One-time programmable PROM 
built-in diagnostics 
Analog Input Module 
 
Feature Description 
Input types 
RTD, T/C, Ohms, mV, Volt, mA.    
See Table 38 for PV Input types and ranges. 
Input Impedance 
10 megohms for T/C and mV inputs; > 1 megohm for volts and 250 ohms for 
mA inputs 
Number of inputs 
8 per module  
Input Device 
Photo-MOSFET Relay  
Isolation 
400 Vdc point-to-point, solid state switching; 1k Vdc to logic 
RTDs are isolated in pairs (I
RTD
 is common to two inputs.) 
Noise Rejection 
Series mode > 60dB 
Common mode > 130 dB at 120 Vac 
Burnout 
T/C, mV, V (except for following ranges) are configurable for Upscale, 
Downscale, Defined Value, or None:  
Volt: -500 mV to 500 mV; -1 V to 1 V; -2 V to 2 V; -5 V to 5 V; 0 V to 10 V; -10 
V to 10 V; inherent to zero volt 
RTD: Inherent Upscale 
MA: Inherent Downscale 
T/C Break Detection 
Via current pulse 
Faulty thermocouple detection 
If greater than 100 ohms, a warning status is provided as an output for the AI 
block 
Accuracy 
Factory configured accuracy - ± 0.1% of range 
Cold Junction accuracy = ± 0.5% of range 
Field calibration accuracy = ± 0.05% of range 
Reference conditions: 
Temperature = 25 °C ± 3 °C (77 °F ± 5 °F) 
Humidity = 45%  to 55% RH non-condensing 
Line voltage = Nominal ± 1 % 
Source resistance = ohm 
Series mode and common mode = 0 V 
Frequency  = Nominal ± 1 % 
Temp. effect on Accuracy 
±0.01% of full scale/°C 
A/D converter 
One per card