Honeywell HC900 User Manual

Page of 228
Specifications - AC Output Module 
168 
  HC900 Hybrid Controller Installation and User Guide 
Revision 5 
  
9/03 
AC Output Module 
 
Feature Description 
Outputs 
8  
Isolation 
Per output; Jumper comb is available for connecting "L1" terminals 
Operating Voltage 
85 Vac to 240 Vac 
Output type 
Triac 
Peak Voltage 
250 Vac 
AC Frequency 
47 to 63 Hz 
Transient Over-voltage 
Protection 
MOV 
ON-Voltage drop 
< 1.5 Vac (> 0.1 A) 
< 3.0 Vac (< 01. A) 
Maximum Load Current 
2 A per point, 8 A max. per module, resistive load 
Maximum Leakage Current 
4 mA (240 Vac, 60 Hz) 
1.2 mA (100 Vac, 60 Hz) 
0.9 mA (100 Vac, 50 Hz) 
Maximum In-rush Current 
60 A for 10 ms 
Minimum Load 
50 mA 
Base Power Required  
218 mA @ 5V 
Response Time  
Off to On: 2 ms + 1/2 cycle 
On to Off: 2 ms + 1/2 cycle 
Fuses  
Replaceable; Wickmann part #3741315041. 3.15 Amp time lag fuse with 
UL/CSA approval for 250 VAC