Appendix B Installation of Remote Termination Panels (RTPs) - Analog Input 
184 
  HC900 Hybrid Controller Installation and User Guide 
Revision 5 
  
9/03 
 
Analog Input 
8 Point Analog Input 
Step Action 
ATTENTION: RTP is not for use with thermocouples. 
ATTENTION: RTP and cables are intended for permanent installation within their own enclosure. 
Mount RTP cable assembly to HC900 Controller (Figure 60). 
• 
Remove appropriate key tabs from terminal block to allow mating with the module. See page 64. 
• 
Connect desired cable to AI module at controller. Choose from: 
900RTC-L010  Remote Terminal Low Voltage Cable Assembly, 1.0 meters long 
900RTC-L025  Remote Terminal Low Voltage Cable Assembly, 2.5 meters long.  
900RTC-L050  Remote Terminal Low Voltage Cable Assembly, 5.0 meters long 
• 
Install AI module label onto the module connector cover. 
• 
Connect shield drain wire to the grounding bars at the base of the HC900 rack.  All field-wiring 
shields must be grounded as described in the shield grounding section (page 60). 
Mount RTP to DIN rail. 
• 
Latch to rail. See page 205. 
• 
Connect cable to RTP.