I/O Module Installation and Wiring - I/O Installation Procedures 
Revision 5 
  HC900 Hybrid Controller Installation and User Guide 
63 
9/03  
I/O Installation Procedures 
Table 14 - Connect Input/Output Wiring 
Step Procedure 
Comments 
 
Reference 
 
 
 
 
 
 
 
Using Rack #, Slot #, 
Channel # data from a 
Hybrid Control Designer 
report and/or from 
documentation aids in 
Appendix A for reference, 
fill in the tagnames on the 
Label for each configured 
I/O Module. 
Be sure to use the 
appropriate label for each 
module type.  
 
Place the appropriate label 
supplied with the module 
(tagname side out) into the 
hinged door for each I/O 
Module.  
Slotted tabs, molded into 
the door at top and bottom, 
hold the label in place.  
 
(Optional): Install jumper 
combs into designated 
Barrier style Terminal 
Blocks, to reduce the 
wiring required to supply 
power:  
Two-position jumper for 
the DC Input Module 
and/or on the DC Output 
Module. 
Ten-position jumper for 
the AC Output Module.  
Five-position jumper (10-
position jumper cut in half) 
for a Relay Output 
Module. 
 
Refer to terminal block wiring diagrams for specific information.