Recommended Cables
To perform thermocouple input, connect a thermocouple element to the terminals. When the wiring distance is long
or when connecting the thermocouple without the element to the terminals, connect via shielded compensating lead
wires.
NOTE
•For I/O other than thermocouple, use polyethylene insulated vinyl sheathed cable
for JCS-364 shielded instruments or equivalent. (general name: twisted shielded
cable for instrument use)
The following cables are recommended.
•A shielded multicore microphone cord (MVVS) may be used, if electromagnetic
induction is comparatively low.
Fujikura 
Cable Co.
2-wire
IPEV-S-0.9mm
× 1P
3-wire
ITEV-S-0.9mm
2
 × 1T
Hitachi Cable 
Co.
2-wire
KPEV-S-0.9mm
2
 × 1P
3-wire
KTEV-S-0.9mm
2
 × 1T
4-3
Chapter 4. WIRING