APC MX28B-2400 User Manual

Page of 54
MX28B-1200   PRODUCT MANUAL 
Revision B 
24 MX28B-1200/2400 
 
5.7.1  External Alarm Inputs 
Four external alarm inputs with assignable priority levels are available.  These alarm inputs 
respond to external dry contact closures between normally open (NO) and common (C) or 
contact openings between normally closed (NC) and C (see Table 5-1). 
Table 5-1.  External Alarm Input Definition 
Table 5-2 shows the external alarm input connection designations.  Connector J4 is located on 
the alarm interface board mounted in the space above the control unit.  Systems are shipped with 
jumper wires connecting each NC and corresponding C contact.  A jumper wire should be 
removed only if the corresponding NC-C contacts are going to be used. 
 
EXTERNAL 
ALARM 
INPUT 
J4 TERMINAL 
DESIGNATION 
(NO-NC-C) 
 
USER ALARM NOTES 
#1 
#2 
#3 
#4 
NO1-NC1-C1 
NO2-NC2-C2 
NO3-NC3-C3 
NO4-NC4-C4 
___________________________ 
___________________________ 
___________________________ 
___________________________ 
Table 5-2.  External Alarm Input Connections 
5.7.2 Alarm Outputs 
There are eight alarms available that provide outputs via Form “C” relay contacts.  The last two 
of these are pre-assigned as the Minor and Major alarm outputs.  The Major relay is energized 
(NO-C contacts closed) during normal (non-alarm) operating conditions; all the other relays 
energize when an alarm condition occurs.  The other six outputs are initially designated as 
“Relay 1” through “Relay 6” (the user may assign more meaningful names if desired).  The 
various system alarm conditions can be assigned to any of the eight alarm outputs. 
Table 5-3 shows the alarm output connection designations.  Connectors J1 and J2 are located on 
the alarm interface board mounted in the space above the control unit.  The relay contacts should 
only be used to switch resistive loads of 0.5 amperes or less at 60 volts or less. 
 
External Alarm Source 
(non-alarm state) 
Connect To Input 
Alarm Terminals 
OPEN 
CLOSED 
NO-C 
NC-C