GE BC5002 User Manual

Page of 50
 
GFK-2023C 
Chapter 6  Controls 
6-3 
6
 
  
 
Front Panel LEDs 
PWR LED 
When the S
HIFT
 key is used to adjust the display settings, the LED goes out. If one of the 
other four keys is also pressed, the LED flashes until the limit of the adjustment range is 
reached.  
The following modes are also displayed: 
■  Green light:  
Indicates ready status (Power ON)  
■  Red light:   
Processor fan speed too slow or stopped 
■  Red flashing: 
Unit overheating 
Note:  The overheating error signal has priority over fan errors and is 
therefore displayed if both errors occur. 
Note:  To ensure that the user has noticed the error signal, the red 
Overheating and Fan Speed LED signals can only be reset by 
restarting the computer. 
CIMPLICITY ME Template for Hardware Monitoring 
When using CIMPLICITY Machine Edition or CIMPLICITY HMI, an OPC driver is provided 
to monitor the PC condition through system status variables. The following features can 
be monitored: 
■  CPU Fan error 
■  Chassis Fan error 
■  CPU over temperature (greater than 50 degrees C) 
■  On board NTC (-127 degree C to +127 degree C) 
TouchScreen 
The operating console is provided with the analog TouchScreen with serial controller, 
which is connected internally to the COM4 serial port. To be able to use the TouchScreen, 
the driver software must be integrated in the relevant operating system (see 
“TouchScreen Driver Installation” in chapter 7).